Power Supply: It requires 5V DC from the backplane.
Operating Temperature: The operating temperature range is 0°C to 55°C.
Relative Humidity: 5% to 95% non - condensing.
Module Size: It is a single - slot module that can be installed in any Series 90 - 30 baseplate.
Communication Interface: Communicates with other devices through the backplane of the Series 90 - 30 PLC.
Cable Connection: A 24 - pin I/O cable is used for building custom - length cables, and there are three different kits available: crimp wire receptacle, solder eyelet receptacle, and IDC (ribbon) receptacle.
Power Supply: It requires 5V DC from the backplane.
Operating Temperature: The operating temperature range is 0°C to 60°C.
Communication Interface: Communicates with other devices through the backplane of the Series 90 - 30 PLC.
Cable Connection: A 24 - pin I/O cable is used for building custom - length cables, and there are three different kits available, including crimp wire receptacle, solder eyelet receptacle, and IDC (ribbon) receptacle.
Operating Temperature: The operating temperature range is 0°C to 60°C.
Relative Humidity: 5% to 95% non - condensing.
Module Size: It is a single - slot module that can be installed in any Series 90 - 30 baseplate.
Communication Interface: Communicates with other devices through the backplane of the Series 90 - 30 PLC.
Cable Connection: A 24 - pin I/O cable is used for building custom - length cables, and there are three different kits available: crimp wire receptacle, solder eyelet receptacle, and IDC (ribbon) receptacle.
Power Supply: It requires 5V DC from the backplane.
Operating Temperature: The operating temperature range is 0°C to 55°C.
Relative Humidity: 5% to 95% non - condensing.
Module Size: It is a single - slot module that can be installed in any Series 90 - 30 baseplate.
Communication Interface: It can communicate with other devices through the backplane of the Series 90 - 30 PLC.
Cable Connection: A 24 - pin I/O cable is used for building custom - length cables, and there are three different kits available: crimp wire receptacle, solder eyelet receptacle, and IDC (ribbon) receptacle.
Power Supply: Requires 24V DC from an isolated 24V DC on the backplane or a user - supplied source, and 5V DC from the backplane. The external supply voltage range is 20 to 30V DC with a 10% external supply voltage ripple.
Isolation: There is 1,500V isolation between the field and logic side.
Output Current Range: Can provide outputs in the ranges of 0 to 20 mA and 4 to 20 mA.
Output Voltage Range: Also supports voltage outputs in the ranges of 0 to 5V and 1 to 5V.
Resolution: The resolution of the converted signal is 12 - bit binary (1 part in 4,096).
Accuracy: At 25 °C (77 °F), the absolute accuracy is ± 8 µA for the 4 to 20 mA range and ± 10 µA for the 0 to 20 mA range.
Power Supply: It requires 24V DC from an isolated 24V DC on the backplane or a user-supplied source, and 5V DC from the backplane.
Isolation: There is 1,500V isolation between the field and logic side.
Output Current Range: The module can provide outputs in the range of 0 to 20 mA.
Resolution: The resolution of the converted signal is 12 bits binary (1 part in 4,096).
Update Rate: Both channels are updated on every scan, which is about 5 milliseconds.
Data Format: User data in the %AQ registers is in a 16-bit 2’s complement format. The 13 most significant bits from the %AQ register are converted to sign magnitude by the PLC and sent to the module.