Bently 3500/15 133292-01
Product Introduction:
Accepts 110 VDC or 125 VDC station batteries and delivers regulated +24 VDC, ±12 VDC and +5 VDC rails. It is used where AC mains are unreliable or where nuclear safety requires battery-only power.
Technical Specifications:
-
Input Voltage: 88-140 VDC
-
Output Rails: +24 VDC @ 5 A, +5 VDC @ 10 A, ±12 VDC @ 1 A
-
Power: 120 W continuous
-
Efficiency: 89 % @ 110 VDC in
-
Ripple: <50 mV pp
-
Hold-up Time: 10 ms @ full load