Bently 1900/65A-00-00-01-00-01 Universal Equipment Monitor
1、 Technical specifications
Sensor Input: Provides 4 sensor inputs, and the software can configure each sensor input to support 2-wire and 3-wire accelerometers, speed sensors, or proximity sensors.
Temperature input: Each temperature input supports E, J, K, and T type thermocouples, as well as 2-wire or 3-wire RTDs.
Output: Provides 6 relay outputs, 4 4-20 mA recorder outputs, and a dedicated buffered output.
Vibration variables: configurable 4-pole high pass and 4-pole low pass from 0.5 Hz to 25 kHz; Envelope Qualcomm: 25Hz to 5kHz, can be configured with 4 poles; Envelope low-pass: 125 Hz to 25 kHz, can be configured with 2 poles; Envelope variable high pass: minimum 0.1 Hz, but greater than 2 poles of envelope variable low pass; Envelope variable low-pass: greater than envelope variable high pass, less than envelope high pass quadrupole; Bias filter: 0.01 Hz 1-pole low-pass; OK filter: 2.4 kHz 1-pole low-pass.