Product Type: Compact Digital Indicator / Single-Loop Controller

Product Introduction:
The UT35-A13501-A is a compact, economical single-loop digital indicating controller from Yokogawa’s UT35 product line. It is designed for basic process variable monitoring and ON/OFF control in cost-sensitive applications. The model code specifies relay output, 4–20 mA input, and 100–240 VAC power.

Detailed content

Model Code Breakdown:

  • UT35 — UT35 Series Digital Indicator, 1/8 DIN size
  • A — Output type: Relay output (ON/OFF control)
  • 13 — Input type: 4–20 mA DC (2-wire)
  • 501 — Input range code: 4–20 mA (0–100% of F.S.)
  • A — Power supply: 100–240 VAC, 50/60 Hz

Technical Specifications:

Parameter Value
Display 5-digit 7-segment LED (14.2 mm), red
Input Signal 4–20 mA DC (2-wire)
Input Impedance 250 Ω
Control Output Relay (SPDT, 250VAC/3A or 30VDC/3A)
Control Mode ON/OFF (with hysteresis)
Setpoints SP1 (main), SP2 (sub-selectable via front panel)
Accuracy ±0.3% of F.S. ± 1 digit
Response Time ≤ 0.5 seconds (display update)
Power Supply 100–240 VAC, 50/60 Hz
Power Consumption ≤ 3 VA
Operating Temperature 0°C to +50°C
Enclosure Rating IP65 (front panel), NEMA 4X
Dimensions (W x H x D) 48 x 96 x 110 mm (1/8 DIN)
Weight Approximately 0.25 kg
Certifications UL, CSA, CE, EAC

Functional Features:

  • Dual setpoint selection (SP1/SP2) via front-panel switch
  • Adjustable hysteresis (0.1–100% of F.S.)
  • Peak/Valley hold function
  • Retransmission output: Optional 4–20 mA retransmission (model-dependent)
  • Burnout detection: Configurable for upscale/downscale/hold
  • Scale programming via front-panel keys

Structural Features:

  • Ultra-compact 1/8 DIN design
  • Snap-in panel mounting
  • Screw-terminal connections (no tools required)
  • Single row of 8 terminals for power, input, and output

Applicable Industries:

  • Food and beverage
  • HVAC
  • Water treatment
  • Light industrial process control
  • OEM equipment

Installation Requirements:

  • Panel cutout: 45 x 92 mm
  • Use shielded cable for input in electrically noisy environments
  • Relay output rated for resistive load only (3A max)
  • Ensure ambient temperature does not exceed +50°C

Usage Precautions:

  • Do not connect inductive loads directly to the relay output (use snubber circuit)
  • Verify input signal polarity before power-on (4–20 mA: + to input+, – to input–)
  • Do not exceed 3A relay contact rating
  • Reset the unit after any power interruption to restore control