Digital guide

You are here:

Yokogawa SAI533-H53

Product Type: Analog Input Card (High-Density)

Product Introduction:
The SAI533-H53 is a 16-channel analog input module for Yokogawa’s CENTUM VP and CENTUM CS distributed control systems. It provides high-density analog signal acquisition for large-scale process control applications. The “H53” suffix specifies the input signal type as 1–5V DC.

Detailed content

Model Code Breakdown:

  • SAI533 — Analog Input Module, 16 channels, CENTUM VP/CS
  • H53 — Input type: 16 channels of 1–5V DC input

Technical Specifications:

Parameter Value
Number of Channels 16 channels
Input Signal 1–5V DC
Input Impedance ≥ 1 MΩ
A/D Resolution 16-bit
Sampling Rate 100 ms per channel (16 channels = 1.6 seconds total)
Accuracy ±0.1% of F.S.
Isolation Channel-to-channel isolation, 500 VDC
Communication Vnet/IP (CENTUM VP), Ethernet (CENTUM CS)
Operating Temperature 0°C to +55°C
Power Supply 5 VDC (bus-powered from I/O base)
Dimensions Standard CENTUM I/O card size: 25 x 160 x 120 mm
Certifications CE, FM, CSA

Functional Features:

  • 16 independent analog input channels with per-channel scaling and engineering units
  • High input impedance (≥ 1 MΩ) minimizes loading on voltage-output transmitters
  • Channel diagnostics: Open circuit, short circuit, out-of-range detection
  • Linearization: Custom linearization tables per channel
  • Retransmission capability via separate output module

Structural Features:

  • Standard CENTUM VP/CS I/O card format
  • Plugs into I/O base unit (Vnet/IP bus)
  • LED indicators per channel group: Normal, Alarm, Fault
  • Software-configurable (no DIP switches required)

Applicable Industries:

  • Oil refineries
  • Chemical plants
  • Power stations
  • Water and wastewater treatment
  • Large-scale process plants using CENTUM VP/CS

Installation Requirements:

  • Insert into designated slot in CENTUM VP/CS I/O base unit
  • Use shielded twisted-pair cable for all 1–5V inputs
  • Keep signal cables separated from power cables by ≥ 200 mm
  • Verify input range matches 1–5V DC configuration before commissioning

Usage Precautions:

  • Do not apply voltage > 5.5V DC to any input channel (risk of damage)
  • Verify input impedance of the field transmitter is compatible (≥ 1 MΩ recommended)
  • Perform annual calibration verification as part of preventive maintenance
  • Do not exceed the maximum channel count per module (16 channels)