BECKHOFF CX1100-0001
Product Name:
BECKHOFF CX1100-0001 Power Supply and Display Module
Overview:
CX1100-0001 supplies 24 V DC power to Beckhoff CX10x0 embedded PC stacks and adds a local alphanumeric display, navigation keys and non-volatile memory for system diagnostics and parameter viewing.
Detailed content
Technical Specifications:
Input power: 24 V DC, -15% to +20%
Maximum power consumption: 2.5 W
Dielectric strength: 500 V eff between supply and internal electronics
Display: FSTN liquid-crystal display, 2 lines x 16 characters, illuminated
Navigation: 4-direction plus 1 confirmation switch
Non-volatile memory: 8 KB NOVRAM
K-bus connection: not included
E-bus connection: not included
IP-Link connection: not included
Connector: 1 x 5-pin open pluggable power connector
Diagnostic LED: 1 x PWR
Recommended fuse: 4 A at 24 V
Dimensions: 45 mm x 100 mm x 91 mm
Weight: approximately 180 g
Operating temperature: 0 °C to +55 °C
Storage temperature: -25 °C to +85 °C
Relative humidity: 95% non-condensing
Protection class: IP20
Functional Features:
Central 24 V DC feed for the CX PC/104 stack
System messages and user text on the 2-line LCD
NOVRAM storage for persistent process and diagnostic data
PC/104-managed display and navigation without external HMI
PWR LED for supply health and short-circuit indication
Performance Parameters:
NOVRAM data retention through power cycles
Display response suitable for boot status, diagnostics and field service
Power loss limited to 2.5 W for the supply/display section
PC/104 16-bit data exchange with the connected CPU module
Material Composition:
Housing: industrial molded plastic with metal mounting elements
Display window: FSTN LCD panel with backlight
PCB: multilayer FR4 control board
Power connector: insulated pluggable terminal with metal contacts
Structural Characteristics:
Narrow CX power module format for stacked installation
Front LCD, navigation keys and PWR LED
Rear PC/104 interface for CPU and system module connection
5-pin open power connector for 24 V DC input wiring
Working Principle:
The module converts external 24 V DC into regulated internal bus power and distributes it over PC/104 to the CPU and expansion modules. The microcontroller-driven LCD and navigation switches present system status; NOVRAM stores values through power interruptions; the PWR LED reflects normal or short-circuit supply conditions.
Installation Requirements:
Mount directly beneath or according to the CX10x0 CPU stack configuration
Use 24 V DC with a 4 A fuse or Class 2 compliant power supply for UL requirements
Tighten the 5-pin power connector to the specified wire size and torque
Ensure PC/104 mating without forced insertion
Usage Precautions:
Check PWR LED behavior; red indication denotes short-circuit condition
Do not apply K-bus or E-bus terminals directly to CX1100-0001 because it has no bus coupler
Avoid moisture, condensation and conductive dust in the cabinet
Backup NOVRAM-relevant data before replacing the module