Digital guide

You are here:

Yokogawa ZR22G-150-S-E-C-R-M-E-A Zirconia Oxygen Analyzer

  • Product Introduction: An in-situ zirconia oxygen analyzer designed for continuous measurement of oxygen concentration in flue gases, enabling efficient combustion control and emissions monitoring in industrial boilers and furnaces.
  • Technical Specifications:
    • Measurement Range: 0.1 to 25 vol% O₂
    • Accuracy: ±0.2 vol% O₂
    • Response Time: ≤5 seconds (90% of step change)
    • Operating Temperature: Probe: 600 to 1400°C; Converter: 0 to 50°C

Detailed content

    • Probe Length: 150mm (insertion depth)
    • Output Signal: 4-20mA DC, HART communication
    • Power Supply: 100-240V AC, 50/60Hz, 15W
    • Protection Class: IP65 (converter), IP66 (probe)
  • Functional Features:
    • In-situ measurement eliminates sample conditioning and reduces maintenance
    • High-temperature zirconia sensor for stable performance in harsh flue gas environments
    • Automatic calibration function for consistent measurement accuracy
    • Built-in diagnostic tools for sensor drift and system fault detection
    • Remote monitoring and control via HART protocol
  • Application Scenarios: Power plants, waste incinerators, cement kilns, and industrial boilers for optimizing combustion efficiency, reducing fuel consumption, and minimizing NOx emissions.