Digital guide

You are here:

YOKOGAWA YS1500-121/A06

Product Introduction:
The YS1500-121/A06 is a compact single-loop controller from Yokogawa’s YS1500 series. It is the smallest model in the YS series, featuring a 1/16 DIN (48 × 48 mm) form factor. The /A06 suffix indicates a specific configuration. The YS1500 provides PID control with universal input in an ultra-compact package suitable for space-constrained panel installations.

Detailed content

Technical Specifications:

  • Controller TypeSingle-loop PID controller
  • Input Type: Universal (TC Type J, K, T, E, B, R, S, L, N, W / RTD Pt100, JPt100, Cu50 / DC Voltage 0–5V, 1–5V / DC Current 4–20mA, 0–20mA / Frequency)
  • Control Output: Relay output (1 SPDT) + 4–20mA DC output (optional, depending on suffix)
  • Alarm Output: 1 alarm output (HIGH, LOW, DEVIATION, BAND)
  • Display4-digit, 7-segment LED (main value) + 4-digit LED (setpoint)
  • Control ModesPID, ON/OFF, 2-Position
  • Scan Rate: 500 ms (0.5 second)
  • Power Supply24 VDC only (some variants accept 100–240 VAC)
  • Power ConsumptionMaximum 3.5 VA
  • Operating Temperature0 to +50 °C (32 to 122 °F)
  • Protection RatingFront panel IP54 / NEMA4 (when panel-mounted with gasket)
  • Dimensions48 mm (W) × 48 mm (H) × 83 mm (D) (1/16 DIN: 45 × 45 mm cutout)
  • Weight: Approximately 0.18 kg

Functional Features:

  • Universal input — auto-detects TC, RTD, mA, V, frequency
  • Simple PID tuning with auto-tuning function
  • Local/Remote switching for setpoint source
  • Output hold function on alarm
  • Bumpless transfer between MAN/AUTO modes
  • Compact size — ideal for dense panel layouts

Performance Parameters:

  • Control Accuracy (PID): ±0.5% of F.S. or ±1 digit
  • Repeatability±0.2% of F.S.
  • Alarm Accuracy: ±1.0% of F.S.

Structural Features:

  • HousingABS resin (UL94 V-0), snap-on front panel
  • Terminal Block: Screw terminal, wire size 0.3–1.5 mm² (AWG 22–16)
  • Mounting1/16 DIN panel clip or DIN rail (35 mm)

Applicable Industries:

  • OEM Equipment — Machine builders requiring compact controllers
  • Packaging Machinery — Seal temperature, fill level control
  • Laboratory Equipment — Oven, incubator temperature control
  • HVAC — Damper actuator control, small zone temperature control
  • Analytical Instruments — Process variable control in analyzer systems

Installation Requirements:

  • Panel cutout: 45 mm × 45 mm for 1/16 DIN mounting
  • Use twisted-pair shielded cable for all analog inputs
  • Maximum cable length: 50 m for mA signal, 100 m for TC (with compensated cable)
  • Ensure 24 VDC supply ripple ≤ 5%

Precautions:

  • Do not exceed rated input signal range — will damage input circuitry
  • Use correct polarity for DC voltage and current inputs
  • Do not apply more than 30 VDC between any terminals
  • Allow 15 minutes warm-up for stable operation