Digital guide

You are here:

YOKOGAWA YS150-012/A06

Product Introduction:
The YS150-012/A06 is a legacy-generation single-loop PID controller from Yokogawa’s YS150 series. It is a compact 1/16 DIN controller designed for basic ON/OFF and PID control applications. The 012 in the model number indicates: 0 = relay output / 1 = alarm output count / 2 = input type variant. The /A06 suffix specifies the faceplate and configuration. The YS150 is a cost-effective solution for simple temperature and process control.

Detailed content

Technical Specifications:

  • Controller TypeSingle-loop ON/OFF or PID controller
  • Input TypeRTD (Pt100, JPt100) / DC Current 4–20mA / DC Voltage 1–5V (limited compared to YS1700/YS1500)
  • Control Output: Relay output (1 SPDT, 250 VAC / 3 A resistive)
  • Alarm Output: 1 alarm output (SPDT relay, 250 VAC / 3 A)
  • Display4-digit 7-segment LED (PV) + 4-digit LED (SV)
  • Control ModesON/OFF (with hysteresis), PID
  • Scan Rate: 1 second (1.0 sec)
  • Power Supply: 100–240 VAC, 50/60 Hz / 24 VDC
  • Power ConsumptionMaximum 4 VA
  • Operating Temperature: 0 to +50 °C (32 to 122 °F)
  • Protection Rating: Front panel IP54 (when properly gasketed)
  • Dimensions48 mm (W) × 48 mm (H) × 82 mm (D) (1/16 DIN: 45 × 45 mm cutout)
  • Weight: Approximately 0.15 kg

Functional Features:

  • 2-control ON/OFF with adjustable deadband
  • PID control with auto-tuning (relay method)
  • Setpoint ramp (soft start)
  • Output limiter (upper and lower limits configurable)
  • Manual output for valve/actuator testing
  • Heating/Cooling control (H/C mode)

Performance Parameters:

  • Control Accuracy (ON/OFF): ±1.0% of F.S. ±1 digit
  • Control Accuracy (PID)±1.0% of F.S. ±1 digit
  • Alarm Accuracy±1.0% of F.S.
  • Relay Life100,000 operations (mechanical) / 300,000 operations (electrical at rated load)

Structural Features:

  • Housing: ABS resin, snap-on front bezel
  • Terminal Block: Screw terminal, wire size 0.5–2.0 mm² (AWG 20–14)
  • Mounting: 1/16 DIN panel clip or DIN rail

Applicable Industries:

  • Small OEM Machines — Injection molding, small furnaces
  • Building Automation — Room temperature control
  • Agriculture — Greenhouse climate control
  • Small Process Plants — Simple tank level/temperature control

Installation Requirements:

  • Panel cutout: 45 mm × 45 mm
  • Use 3-wire RTD configuration for Pt100 inputs
  • For 4–20mA inputs, ensure loop power supply voltage ≥ 18 VDC
  • Keep input wiring away from power cables (minimum 100 mm separation)

Precautions:

  • Do not use for safety-critical (SIL) applications — this is a basic controller
  • Maximum load on relay: 3 A resistive, 1.5 A inductive at 250 VAC
  • Do not exceed 125 VDC or 250 VAC across relay contacts
  • Replace controller if front panel display becomes unreadable (indicates internal degradation)