Product Introduction:
The UT55A is a compact, high-accuracy digital indicating controller from Yokogawa’s UTAdvanced product family. It is designed for temperature, voltage, current, and process signal monitoring with a large 7-segment LED display. The UT55A-040-110 configuration specifies a 4–20 mA input with 100–240 VAC power supply.

Detailed content

Model Code Breakdown:

  • UT55A — UTAdvanced Digital Indicator, 1/4 DIN size
  • 040 — Input type: 4–20 mA DC (2-wire transmitter)
  • 110 — Power supply: 100–240 VAC, 50/60 Hz

Technical Specifications:

Parameter Value
Display 7-segment LED, 5 digits, 14.2 mm digit height (red)
Input Signal 4–20 mA DC (2-wire)
Input Impedance 250 Ω
Measurement Accuracy ±0.1% of F.S. (±1 digit)
Sampling Period 100 ms (200 ms for filtering option)
Power Supply 100–240 VAC, 50/60 Hz (±10%)
Power Consumption ≤ 5 VA
Output Options Relay (ON/OFF), Voltage Pulse, Current (4–20 mA), Communication
Control Modes ON/OFF, PID (with optional output modules)
Alarm Outputs 2 alarm outputs (AL1, AL2), adjustable hysteresis
Communication RS-485 (Modbus RTU)
Operating Temperature 0°C to +50°C
Enclosure Rating IP65 (front panel), NEMA 4X equivalent
Dimensions (W x H x D) 96 x 96 x 110 mm (1/4 DIN)
Weight Approximately 0.55 kg
Certifications UL, CSA, CE, EAC

Functional Features:

  • Universal input scaling (linear, square root, custom)
  • Programmable setpoints (SP1, SP2 with selector)
  • Auto-tuning PID function (with CNT module)
  • Dual alarm outputs with independent setpoints and hysteresis
  • Ladder sequence program (up to 100 steps)
  • Retransmission function for output signal mirroring
  • Peak/Valley hold display capability

Structural Features:

  • 1/4 DIN panel-mount design
  • Screw-terminal connections (no tools required for wiring)
  • Transparent front panel with LED display behind protective window
  • Remote indicator model available

Applicable Industries:

  • Food and beverage processing
  • Pharmaceutical manufacturing
  • Water and wastewater treatment
  • HVAC systems
  • General process industries

Installation Requirements:

  • Cutout size: 92 x 92 mm for panel mounting
  • Ensure adequate clearance for heat dissipation
  • Use shielded twisted-pair cable for input signals in electrically noisy environments
  • Ground the panel chassis to earth ground

Usage Precautions:

  • Do not apply voltage exceeding 30 VDC to the input terminals
  • Verify input signal range matches the configured scaling before operation
  • Do not exceed the maximum ambient temperature of +50°C
  • Replace batteries (if applicable to variant) every 2 years for memory backup