Digital guide

You are here:

Yokogawa UT35A-201-10

Model Number: UT35A-201-10

Product Introduction:
The Yokogawa UT35A-201-10 is a 1/8 DIN-sized digital panel meter with built-in PID control functionality. The 201 code indicates 2 universal inputs with relay output. The 10 suffix specifies 100–240 V AC power supply. This compact controller is designed for basic process monitoring and single-loop control applications where space is at a premium.

Detailed content

Technical Specifications:

  • Input Channels: 2 universal inputs (TC, RTD, mV, V, mA)
  • Output Type: 1 relay output (SPDT)
  • Power Supply: 100–240 V AC (50/60 Hz) — indicated by “10”
  • Control Mode: ON/OFF control with PID option
  • Display: 5-digit, 7-segment LED (14 mm digit height, red)
  • Accuracy: ±0.1% of reading + 1 digit (DC voltage/current input)
  • Input Types Supported: K, J, T, E, B, R, S, L, N thermocouples; Pt100, JPt100 RTDs; 0–100 mV, 0–5 V, 1–5 V, 0–10 V, 4–20 mA, 0–20 mA
  • Control Output: 1 relay (3 A at 250 V AC, 30 V DC)
  • Alarm Outputs: 2 alarm outputs (selectable: SP, LH, LL, DH, DL, deviation)
  • Response Time: 250 ms (typ.)
  • Operating Temperature: 0 to 50 °C (32 to 122 °F)
  • Panel Cutout: 48 × 96 mm (1/8 DIN × 2, or 96 × 48 mm)
  • Depth: 75 mm (2.95 in)
  • Weight: Approximately 200 g (0.44 lb)
  • Protection Rating: IP20 (front panel), IP10 (rear)

Functional Features:

  • Universal Input: Any input channel accepts any sensor type (thermocouple, RTD, mV, V, mA)
  • Heater Burnout Alarm (HBA): Detects open heater circuit in temperature applications
  • Loop Break Alarm (LBA): Detects sensor disconnection
  • Remote Setpoint (RSP): External setpoint via analog input or digital communication
  • Manual Reset: Operator-initiated reset after alarm condition clears
  • Event Memory: Records up to 100 events with timestamps
  • Scaling: Programmable input and output scaling (linear, square root)

Performance Parameters:

  • Input Impedance (Voltage): 10 MΩ minimum
  • Input Impedance (Current): 250 Ω
  • Relay Contact Rating: 3 A resistive at 250 V AC, 30 V DC
  • Insulation Resistance: 100 MΩ minimum at 500 V DC
  • Dielectric Strength: 1500 V AC for 1 minute (input to output to power)
  • EMC Compliance: EN 61326-1
  • Sampling Rate: 5 times per second

Structural Features:

  • Ultra-compact 1/8 DIN format (48 × 96 mm)
  • Snap-in mounting with friction fit
  • Rear-mounted screw terminal block
  • Transparent front cover with LED display window
  • Low-profile design (75 mm depth) for shallow panels

Working Principle:
The UT35A receives process signals on its 2 universal input channels. The internal 16-bit A/D converter digitizes the signal, and the microprocessor applies linearization for thermocouple/RTD inputs. The PV is compared to the SP using ON/OFF or PID control logic. The relay output switches based on the control deviation. HBA and LBA functions continuously monitor input circuit integrity.

Advantage Highlights:

  • Ultra-Compact Size: 1/8 DIN format saves 75% panel space versus 1/4 DIN controllers
  • Universal Inputs: No need to stock multiple meter types; one model covers all sensor types
  • Built-in HBA/LBA: Unique alarm functions prevent undetected sensor failures
  • 100–240 V AC Operation: Wide power supply range eliminates need for external transformers in most regions
  • Cost-Effective: Lower cost than UT55A while maintaining core control functionality

Applicable Industries:

  • OEM equipment manufacturing
  • HVAC systems
  • Food processing equipment
  • Packaging machinery
  • Small-scale chemical batch processes
  • Laboratory equipment
  • Building automation

Installation Requirements:

  • Panel cutout: 44 × 92 mm minimum, 48 × 96 mm nominal
  • Mounting depth clearance: 75 mm from front of panel
  • Use 22–14 AWG wire for terminal connections
  • Ensure ambient temperature does not exceed 50 °C
  • Provide adequate ventilation behind panel (minimum 50 mm clearance)

Usage Precautions:

  • Verify input type setting matches actual sensor before applying power
  • Do not exceed 3 A relay load rating
  • Calibrate annually to maintain ±0.1% accuracy
  • Do not install in direct sunlight or environments exceeding 50 °C ambient
  • Use shielded cables for mV and thermocouple inputs to minimize noise

You may also like