Digital guide

You are here:

Yokogawa UR1BG3-008-0102-008/Z

Product Overview:
The UR1BG3-008-0102-008/Z is a safety-rated I/O interface module for the Yokogawa ProSafe-RS Safety Instrumented System. The configuration 008-0102-008/Z indicates: 008 = 8-channel digital input, 0102 = specific module variant/channel grouping, 008/Z = additional 8-channel configuration with zone-specific termination. This module provides SIL3-certified digital input signal acquisition from field safety devices (emergency stop buttons, limit switches, gas detectors).

Detailed content

Technical Specifications:

Parameter Specification
Module Type Safety Digital Input Module
Number of Channels 8 channels (008)
Input Type Dry contact (N.O./N.C.), 24VDC, 48VDC (configurable per channel)
Input Voltage Range 12-48 VDC (dry contact) or 18-48 VDC (wet contact)
Input Current < 5 mA per channel (wet contact), 0 mA (dry contact)
Debounce Time 20 ms (configurable: 10-100 ms)
Diagnostic Coverage > 99% (wire break, short circuit, stuck-at detection)
Safety Rating SIL3 (IEC 61508), SIL3 (IEC 61511)
Isolation Voltage 1500 VAC (channel-to-channel, channel-to-backplane)
Operating Temperature 0°C to +60°C (+32°F to +140°F)
Power Supply 24VDC (from safety bus)
Power Consumption < 2.0 W (total module)
Dimensions (W×H×D) 25 × 120 × 120 mm (approx.)
Weight Approximately 0.2 kg
Certifications ATEX, IECEx, FM, CSA, TÜV

Functional Features:

  • Per-channel diagnostics: Wire break, short to positive, short to negative, stuck-at-0, stuck-at-1
  • Cross-monitoring between redundant channels for SIL3 compliance
  • Fail-safe default state configurable per channel (Normal Open / Normal Closed)
  • LED status indicators per channel group (4 LEDs per group of 8)
  • Online insertion/removal supported
  • Event timestamp accuracy: ±1 ms

Material Composition:

  • Housing: Flame-retardant PBT plastic (UL94 V-0)
  • Terminal blocks: Phosphor bronze, tin-plated
  • PCB: FR-4 with conformal coating (IP20 protection)
  • ConnectorsPluggable terminal blocks for field wiring

Applicable Industries:

  • Oil & Gas — Emergency shutdown (ESD) button input, gas detector status
  • Chemical Plants — Safety interlock monitoring (door switches, level switches)
  • Power Generation — Turbine protection system inputs
  • Mining — Personnel safety system inputs (man-down, evacuation switches)

Installation Requirements:

  • Install in ProSafe-RS compatible I/O rack (UR1BG3 bus)
  • Use shielded twisted-pair cable for all digital input connections
  • Shield ground at DCS end only
  • Maintain 30 mm spacing between modules for ventilation
  • Connect field device common (0V) to module common terminal

Usage Precautions:

  • Never exceed 48VDC on any input channel
  • Dry contact inputs must not have external power applied
  • Perform proof test at intervals ≤ 12 months per IEC 61511
  • Replace module if diagnostic coverage degrades below 99%
  • Document all channel configurations in safety lifecycle management system