YOKOGAWA UP55A-000-110
Manufacturer: Yokogawa Electric Corporation
Product Introduction:
The UP55A-000-110 is a 6-channel universal input paperless recorder from Yokogawa’s UP55A series. It is a 1/8 DIN (96 × 48 mm) panel-mount recorder designed for multi-channel data acquisition, display, recording, and alarm monitoring in industrial process environments. The “000” denotes 6 universal input channels, and “110” denotes 100–240 V AC power supply.
Detailed content
Measurement Principle:
The recorder uses high-speed A/D converters (24-bit) to digitize analog input signals from thermocouples, RTDs, DC voltage, DC current, and frequency sensors. Data is processed, displayed in real-time on the LCD, stored in internal NAND flash memory, and can be transmitted via RS-232C, RS-485, or Ethernet (Modbus TCP) to a host system.
Technical Specifications:
| Parameter | Specification |
|---|---|
| Model | UP55A-000-110 |
| Number of Channels | 6 Universal Input Channels (000 = 6 ch) |
| Input Types | TC (J, K, T, E, R, S, B, N, W), RTD (Pt100, Pt1000, Cu50, JPt100), DC V (0–100 mV, 0–1 V, 0–5 V, 0–10 V), DC mA (0–20 mA, 4–20 mA), Frequency (0–1 kHz) |
| Display | 128 × 64 pixel Monochrome LCD with White LED Backlight |
| Recording Interval | 0.1 sec to 3600 sec (selectable) |
| Recording Memory | 64 MB internal flash (approx. 20 days at 1 sec interval for 6 ch) |
| Accuracy (DC V) | ±0.1% of F.S. ±1 digit |
| Accuracy (DC mA) | ±0.1% of F.S. ±1 digit |
| Accuracy (TC/RTD) | ±0.1% of reading or ±1°C (whichever is greater) |
| Power Supply | 100–240 V AC, 50/60 Hz (110) |
| Communication | RS-232C, RS-485 (Modbus RTU), Ethernet (Modbus TCP/EtherNet/IP) |
| Alarm Outputs | 4 Relay Outputs (alarm, batch, etc.) |
| Analog Output | 1 Channel (4–20 mA DC, selectable) |
| Protection Class | NEMA 4 / IP66 (front panel) |
| Dimensions | 96 × 48 × 118 mm (W × H × D) |
| Cutout Size | 92 × 44 mm (1/8 DIN) |
| Weight | Approx. 0.4 kg |
| Approvals | CE, UL, CSA, FM (for hazardous areas — check specific variant) |
Structural Features:
- 1/8 DIN (96 × 48 mm) panel-mount form factor — extremely space-efficient
- Monochrome LCD with high visibility in all lighting conditions
- Front panel keypad with membrane keys for local operation
- SD card slot (optional) for data backup and transfer
- 4 relay alarm outputs with programmable setpoints
- Compact depth (118 mm) — fits in shallow panels
Performance Parameters:
| Parameter | Value |
|---|---|
| Sampling Rate | 200 ms per channel (6 ch), 100 ms per channel (3 ch) |
| Data Retention | 10 years (with SD card backup) |
| Number of Recordings | Up to 100 recording files |
| Batch Recording | Yes — up to 100 batches |
| Event Recording | Yes — captures alarm events with timestamp |
| Remote Display | Yes — via Web browser (Ethernet models) |
| Power Consumption | ≤ 8 VA |
| Operating Temperature | 0°C to +50°C (32°F to +122°F) |
| Storage Temperature | -20°C to +60°C (-4°F to +140°F) |
Key Advantages:
- 6 universal input channels in 1/8 DIN size — highest channel density in its class
- Supports ALL major sensor types — TC, RTD, mA, V, frequency — no need for multiple recorders
- Ethernet connectivity — remote monitoring via web browser without additional software
- NAND flash memory — no moving parts, no paper, no ink
- SD card backup — easy data archival and transfer
- Batch recording function — ideal for batch process industries
Applicable Industries:
- Chemical and Petrochemical Processing
- Pharmaceutical Manufacturing
- Food and Beverage (Batch Processes)
- Power Generation
- HVAC and Building Automation
- Environmental Monitoring
- Laboratory and R&D
Installation Requirements:
- Cut panel opening to 92 × 44 mm for 1/8 DIN mounting
- Secure with mounting clips or screws (provided)
- Connect all input signals using appropriate thermocouple extension wire or shielded cable
- For RS-485 communication: use shielded twisted-pair cable; terminate with 120 Ω resistor at the last device
- For Ethernet: use Cat5e or higher cable; connect to a managed switch for best performance
- Ground the recorder chassis to the panel ground bus
Usage Precautions:
- Do not exceed the rated input voltage/current for any channel — this will damage the A/D converter
- Use correct thermocouple type settings — mismatched type settings cause large errors
- Perform cold junction compensation (CJC) verification periodically
- Back up data to SD card before firmware updates
- Do not block the ventilation slots on the top and bottom of the unit
- Do not apply power with incorrect voltage — 110 = 100–240 V AC only
- Replace the internal backup battery (if equipped) every 2 years to preserve clock and settings