Digital guide

You are here:

Yokogawa SR1400A02

Product Category: Serial Interface Communication Card

Product Overview:
The SR1400A02 is a dual-port serial communication module for the CENTUM VP and CS3000 DCS platforms. It provides RS-232C and RS-485 communication interfaces for connecting the DCS to serial devices such as modems, printers, barcode readers, PLCs, and other legacy equipment.

Detailed content

Technical Specifications:

  • Model Code: SR1400A02
  • Communication Ports: 2 ports (configurable as RS-232C or RS-485)
  • RS-232C Specifications:
    • Baud Rate: 110, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
    • Data Bits: 7 or 8
    • Parity: None, Even, Odd
    • Stop Bits: 1 or 2
    • Connector: DB-9 (male)
  • RS-485 Specifications:
    • Baud Rate: Up to 115200 bps
    • Mode: Half-duplex / Full-duplex
    • Connector: Terminal block (screw-type)
  • Power Supply: 5 VDC (supplied from I/O bus, no external power required)
  • Power Consumption: ≤ 1.5 W
  • Operating Temperature Range: 0°C to +55°C
  • Storage Temperature Range: -20°C to +70°C
  • Relative Humidity: 5% to 95% RH (non-condensing)
  • Isolation: 500 VDC (between port and bus)
  • MTBF: ≥ 80,000 hours
  • Dimensions (W × H × D): 25 mm × 90 mm × 100 mm (approx.)
  • Weight: Approximately 130 g
  • Mounting Method: DIN rail (35 mm) or card cage mounting (CENTUM VP I/O station)

Functional Features:

  • Dual independent serial ports for simultaneous communication with two devices
  • Supports Modbus RTU (Master/Slave) protocol over RS-485
  • Supports printer output via RS-232C for alarm and event logs
  • Buffer memory: 256 bytes per port (TX/RX)
  • Auto-baud rate detection on RS-232C port
  • Compatible with CENTUM VP operation station (HIS, ENG, OPR) for data logging

Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Water/Wastewater, Pharmaceutical, Food & Beverage

Installation Requirements:

  • Install in CENTUM VP I/O station or communication rack
  • Use shielded cable for RS-485 connections (max 1200 m at 9600 bps)
  • Terminate RS-485 bus with 120 Ω resistor at both ends
  • Set DIP switches for baud rate, parity, and address configuration

Precautions:

  • Do not connect RS-232C and RS-485 devices to the same port simultaneously
  • Maximum cable length for RS-232C: 15 m
  • Ensure proper grounding of RS-485 shield at one end only
  • Do not exceed 115200 bps to maintain signal integrity