Yokogawa SD1075B02-2PO

Product Series: SD1075 — ProSafe-RS Series Analog I/O Module

Product Overview:
The SD1075B02-2PO is a 4-channel analog output module from the ProSafe-RS Safety Instrumented System. The B02-2PO variant designation indicates a specific configuration providing 2-channel pulse output capability in addition to standard 4-20mA analog outputs. This module delivers SIL2/SIL3 certified output signals for final control elements in safety loops.

Detailed content

Technical Specifications:

Parameter Specification
Module Type 4-channel analog output (4-20mA DC)
Pulse Output Channels 2 channels (2PO)
Output Resolution 16-bit D/A converter
Output Accuracy ±0.1% of span (typical)
Output Load Resistance 0 to 600 Ω (4-20mA mode)
Pulse Output Type Open-collector transistor, 30VDC max, 50mA max
Pulse Frequency 0 to 1000 Hz (adjustable)
Isolation Voltage 1500 VAC (channel-to-channel, channel-to-backplane)
Safety Rating SIL2 / SIL3 (IEC 61508, IEC 61511)
Operating Temperature 0°C to +60°C (+32°F to +140°F)
Power Consumption < 3.5 W per module
Dimensions (W×H×D) 25 × 120 × 120 mm (approx.)
Weight Approximately 0.2 kg

Functional Features:

  • Dual-redundant output drivers for SIL3 applications
  • Fail-safe output states configurable per channel (High/Low/Last Value)
  • Online calibration without removing module from rack
  • Diagnostic coverage > 99% for output channel failures
  • Short-circuit protection on all output channels
  • Loop break detection with alarm notification

Applicable Industries:

  • Oil & Gas — Emergency shutdown valve (ESDV) control
  • Chemical Processing — Safety relief valve actuation
  • Power Generation — Turbine trip signal output
  • Refineries — Fire and gas system actuation

Installation Requirements:

  • Install in ProSafe-RS compatible chassis/rack
  • Use shielded twisted-pair cables, shield grounded at one end only
  • Maintain minimum 30 mm spacing between modules for heat dissipation
  • Connect loop power supply per module specifications (24VDC nominal)

Usage Precautions:

  • Do not exceed 600 Ω total loop resistance in 4-20mA mode
  • Verify pulse output voltage rating before connecting to solenoid valves
  • Perform output proof test at recommended intervals (≤ 12 months)
  • Never bypass safety diagnostics or disable fault detection features
  • Ensure proper termination of unused channels to prevent floating signals