Digital guide

You are here:

Yokogawa SD1050A04-2SN

Product Category: Redundant/Non-Redundant Power Supply Unit

Product Overview:
The SD1050A04-2SN is a 24 VDC power supply module designed for the CENTUM VP and CS3000 Distributed Control Systems (DCS) manufactured by Yokogawa. It provides regulated 24 VDC output at 4 Amperes to power I/O cards, communication modules, and field instruments within the DCS I/O station.

Detailed content

Technical Specifications:

  • Model Code: SD1050A04-2SN
  • Output Voltage: 24 VDC (±5%)
  • Output Current: 4 A (maximum)
  • Output Power: 96 W (maximum)
  • Input Voltage: 100 VAC to 240 VAC (50/60 Hz) or 24 VDC (optional)
  • Input Frequency: 50 Hz / 60 Hz (auto-detection)
  • Efficiency: ≥ 85% (typical at full load)
  • Ripple & Noise: ≤ 150 mVp-p
  • Isolation Voltage: 1500 VAC (input to output, 1 minute)
  • Operating Temperature Range: 0°C to +55°C
  • Storage Temperature Range: -20°C to +70°C
  • Relative Humidity: 5% to 95% RH (non-condensing)
  • Protection Features: Overcurrent protection, overvoltage protection, short-circuit protection, thermal shutdown
  • MTBF (Mean Time Between Failures): ≥ 100,000 hours
  • Dimensions (W × H × D): 25 mm × 90 mm × 100 mm (approx.)
  • Weight: Approximately 200 g
  • Mounting Method: DIN rail (35 mm) mounting

Functional Features:

  • Provides stable 24 VDC to all I/O cards in the CENTUM VP I/O station
  • Built-in overcurrent protection with automatic recovery
  • LED indicators: POWER (green), FAULT (red)
  • Supports hot-swap capability in redundant configurations
  • Compatible with CENTUM VP I/O stations (AIH, AOH, ASH, etc.)

Structural Features:

  • Metal housing with ventilation slots for forced-air cooling
  • Terminal block connectors for AC input and DC output
  • Front-facing LED status display
  • Screw-type DIN rail mounting bracket

Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Chemical Processing, Water Treatment, Steel Manufacturing, Pulp & Paper

Installation Requirements:

  • Install in CENTUM VP I/O station with adequate ventilation
  • Connect AC power input with proper circuit breaker (rated ≥ 5 A)
  • Wire DC output terminals using wire gauge AWG 14 to AWG 22
  • Ensure cabinet earth grounding is connected to chassis ground terminal

Precautions:

  • Do not exceed 4 A output current to prevent damage
  • Verify input voltage range matches local power supply (100-240 VAC)
  • Allow minimum 10-minute warm-up before loading full current
  • Replace fuse only with Yokogawa-specified fuse (T3.15A, 250V)

You may also like