Yokogawa SC4A-S-PR-NN-0 10-10-T1
Product Category: Universal Analog Signal Converter
Product Overview:
The SC4A-S-PR-NN-0 10-10-T1 is a universal signal converter from Yokogawa’s SC4A product line. It converts various analog process signals into isolated standardized outputs. The configuration code indicates: S = Standard type, PR = Process recording support, NN = No network communication, 0 = Base configuration, 10-10 = Specific range setting, T1 = Terminal block type.
Detailed content
Technical Specifications:
- Input Signal: 4–20 mA DC / 1–5 V DC / 0–10 V DC (selectable via DIP switch)
- Output Signal: 4–20 mA DC / 1–5 V DC / 0–10 V DC (selectable via DIP switch)
- Power Supply Voltage: 24 VDC (±10%)
- Accuracy: ±0.1% of span
- Temperature Drift: ±0.005%/°C
- Insulation: Triple isolation (input / output / power supply)
- Insulation Resistance: ≥100 MΩ at 500 VDC
- Dielectric Strength: 1500 VAC for 1 minute
- Operating Temperature: -10°C to +55°C
- Response Time: ≤100 ms (typical)
- Mounting: 35 mm DIN rail (EN 50022)
- Width: 22.5 mm
Functional Features:
- Universal input/output — accepts and outputs current or voltage signals
- Triple galvanic isolation — input, output, and power are fully isolated
- No communication function (standalone operation)
- Process recording support (PR) — compatible with SCADA recording systems
- DIP switch configuration for input/output type selection
- Zero and span adjustment via front-panel potentiometers
Material Composition:
- Housing: Flame-retardant polycarbonate/ABS blend (UL94 V-0)
- Terminal Blocks: Phosphor bronze, tin-plated
- PCB: Conformal-coated epoxy glass
Structural Characteristics:
- Dimensions: 22.5 mm × 90 mm × 112.5 mm (W × H × D)
- Terminal Type: T1 screw clamp terminals (AWG 22–12)
- Weight: Approximately 150 g
Working Principle:
The SC4A accepts an analog input signal (current or voltage), conditions it through precision signal conditioning circuitry, and outputs a proportional isolated analog signal. The triple isolation barrier uses transformer/optocoupler technology to ensure complete electrical separation between input, output, and power circuits.
Key Advantages:
- ±0.1% high accuracy — superior to most competitors
- Triple isolation eliminates all ground loop issues
- Universal I/O — one device replaces multiple converter types
- Front-panel adjustment — zero and span accessible without removing from panel
Applicable Industries:
- General Industrial Process Control
- HVAC Systems
- Building Automation
- Power Plants
- Pulp & Paper
Installation Requirements:
- Install on 35 mm DIN rail (EN 50022)
- Use shielded cables with shield grounded at one end only
- Set input/output ranges via DIP switches before commissioning
- Verify polarity on all connections
Usage Precautions:
- Do not connect input and output grounds together
- Maximum ambient temperature is +55°C — do not exceed
- Do not apply signals exceeding 30 VDC or 25 mA to any terminal
- Ensure adequate ventilation spacing (10 mm minimum above/below)