Product Introduction:
The PSCCM24AAN is a combined power supply and communication module for the Yokogawa FA-M3 and F3 Series Programmable Logic Controllers. This module provides 24 V DC regulated power to the PLC backplane and I/O modules while also serving as a communication gateway for programming and data exchange. The “24” indicates 24 V DC output, “AA” specifies the communication protocol variant (typically Modbus RTU/TCP or proprietary), and “N” denotes the noise filter configuration.

Detailed content

Technical Specifications:

  • Input Voltage: 100 to 240 V AC, 50/60 Hz (universal)
  • Output Voltage24 V DC (regulated, ±2% tolerance)
  • Output Current: 3 A maximum (72 W total)
  • CommunicationRS-232C, RS-485 (Modbus RTU master/slave), Ethernet (10/100 Base-TX, Modbus TCP)
  • Protocol SupportModbus RTU, Modbus TCP, Yokogawa F-Link (proprietary)
  • Isolation: 1500 V DC between power section and communication section
  • Operating Temperature0°C to +55°C
  • Protection: Overcurrent (3.5 A fuse), overvoltage, reverse polarity, short-circuit
  • MTBF: ≥100,000 hours
  • Compliance: UL 508, CE, CSA C22.2 No. 142

Functional Features:

  • Dual function: Provides backplane power AND communication interface — eliminates need for separate communication modules
  • Web server built-in — allows remote monitoring and parameter changes via standard web browser
  • E-mail alarm notification — configurable alarm-triggered e-mail with data attachment
  • Firmware update via Ethernet or USB — no need to remove module from rack
  • LED indicators: Power OK (green), Communication (yellow blinking), Fault (red)

Performance Parameters:

Parameter Value
Output Ripple ≤100 mV peak-to-peak
Line Regulation ±1% (100–240 V AC)
Load Regulation ±2% (0 to 3 A)
RS-485 Speed Up to 115.2 kbps
Ethernet Speed 10/100 Mbps auto-negotiation
EMC Compliance IEC 61131-2 (emission and immunity)

Material Composition:

  • Housing: Flame-retardant ABS plastic (UL 94 V-0)
  • PCBFR-4, 6-layer, with conformal coating
  • Terminals: Phoenix Contact-compatible screw terminals, 4 mm pitch
  • Ethernet ConnectorRJ-45 with integrated magnetics (isolation transformer)
  • Fuse3.5 A slow-blow, 250 V AC (replaceable)

Structural Characteristics:

  • Form Factor: FA-M3 / F3 standard module
  • Dimensions: 98 mm (W) × 130 mm (H) × 90 mm (D)
  • Weight: Approximately 0.5 kg
  • Mounting: DIN rail or backplane insertion in FA-M3 / F3 rack
  • Connector (backplane side): FA-M3 / F3 standard 48-pin connector

Working Principle:
The module accepts 100–240 V AC input, rectifies it via a bridge rectifier and PFC stage, then uses a high-frequency isolated flyback DC-DC converter (typically 200 kHz PWM) to generate regulated 24 V DC for the PLC backplane. The communication section uses a dedicated Ethernet controller ASIC with an integrated TCP/IP stack and Modbus engine, connected to the PLC CPU via the backplane bus. The RS-485 transceiver is galvanically isolated from the power section using a digital isolator IC.

Key Advantages:

  • Combined power + communication in one module — reduces rack space by 1 slot
  • Built-in web server — enables remote maintenance without specialized software
  • E-mail alarm — proactive notification before operator reaches control room
  • 3 A output capacity — sufficient to power CPU + up to 8 I/O modules

Applicable Industries:

  • Oil and gas SCADA (remote well monitoring)
  • Water treatment (remote pump station control)
  • Manufacturing (distributed I/O with Ethernet backbone)
  • Building automation (BACnet/Modbus integration)
  • Renewable energy (solar/wind farm remote monitoring)

Installation Requirements:

  • Install in FA-M3 or F3 PLC rack (slot 0 or dedicated power/comm slot)
  • Connect AC input to dedicated circuit breaker (rated 5 A, C-curve)
  • Connect Ethernet cable to managed switch (Cat 5e or better, max 100 m)
  • Bond chassis ground to plant earth ground (< 4 Ω impedance)
  • Configure IP address, subnet mask, and gateway in F3/FA-M3 engineering software

Usage Precautions:

  • Do not exceed 3 A total output current — fuse will blow, module will shut down
  • Use shielded Cat 5e/Cat 6 cable for Ethernet in electrically noisy environments
  • Set unique IP addresses for each PSCCM24AAN on the same network segment
  • Update firmware only from Yokogawa-approved sources — corrupted firmware will brick the module
  • Replace the 3.5 A fuse only with the exact same rating (250 V AC, slow-blow)