Digital guide

You are here:

Yokogawa GX90XA‑10‑L1N‑CC

  • Product Name: Analog Input Module for GM10 Modular Data Acquisition System
  • Product Series: GX90XA Series Universal Analog Input Modules
  • Product Introduction: Low‑withstand‑voltage 10‑channel universal analog input module for Yokogawa GM10 modular data acquisition recorder system, used for multi‑channel industrial parameter synchronous acquisition.

Detailed content

  • Technical Specifications:
    • Number of Input Channels: 10 channels per module
    • Input Type: DC voltage, DC current (with external shunt resistor), thermocouple, RTD resistance thermometer, contact signal
    • Module Grade: L1 low‑withstand‑voltage type; N industrial standard grade
    • Connector Type: CC screw‑type M3 terminal block
    • Measuring Cycle: Shortest 100 ms sampling period
    • Input Signal Range: DCV 20 mV‑100 V; standard signal 0.4‑2 V, 1‑5 V; resistance 20‑2000 Ω; compatible with multi‑type thermocouples and RTDs
  • Function Features: Multi‑type signal universal input; per‑channel independent A/D conversion; channel‑to‑channel electrical isolation; support thermocouple cold‑junction compensation; built‑in open‑circuit detection function; plug‑and‑play modular design.
  • Performance Parameters: Measurement accuracy ±0.02% full scale; isolation withstand voltage 500 V AC; sampling resolution 16‑bit; long‑term stability ±0.05% full scale per year.
  • Material Composition: Industrial‑grade high‑precision PCB; copper alloy screw terminals; flame‑retardant plastic housing; low‑drift signal acquisition chips; anti‑interference shielding materials.
  • Structural Characteristics: Standard GM10 system rack‑mount modular structure; screw‑type wiring terminals; compact channel‑arrangement layout; compatible with all GM10 series data acquisition mainframes.
  • Working Principle: Collect analog signals from on‑site sensors/transmitters, convert analog signals to digital signals via independent high‑precision A/D converter per channel, transmit digital data to GM10 mainframe for data processing and storage.
  • Advantage Highlights: High‑density multi‑channel synchronous acquisition; wide signal type compatibility; high‑precision measurement; strong anti‑interference performance; flexible modular expansion for channel quantity.
  • Applicable Industries: Industrial process monitoring, power system testing, petrochemical parameter acquisition, metallurgical equipment monitoring, environmental multi‑parameter testing, laboratory multi‑channel data recording.
  • Installation Requirements: Installed in GM10 series modular rack; ensure good contact with mainframe backplane; ambient temperature 0–50 °C; avoid strong electromagnetic interference sources nearby.
  • Usage Precautions: Correctly set input signal type and range per channel; use shielded cables for signal wiring; regularly calibrate module measurement accuracy; avoid over‑voltage input damage.