Digital guide

You are here:

Yokogawa FX1012-4-2-L

Product Overview:
The FX1012-4-2-L is a 4-channel, 2-wire transmitter input module for the Yokogawa FAST/TOOLS distributed control system. The designation breaks down as: FX1012 (module type), 4 (4 channels), 2 (2-wire 4-20mA input), L (low-power/linear configuration). This module accepts signals from 2-wire loop-powered transmitters (pressure, temperature, flow, level).

Detailed content

Technical Specifications:

Parameter Specification
Number of Channels 4 channels
Input Signal Type 2-wire 4-20mA DC (loop-powered)
Input Impedance 250 Ω (built-in precision resistor)
Measurement Accuracy ±0.1% of span (typical)
Resolution 16-bit A/D converter (65,536 steps)
Common Mode Rejection > 100 dB at 50/60 Hz
Isolation Voltage 1500 VAC (channel-to-channel, channel-to-backplane)
Loop Power Supply 24VDC (provided by module, max 30VDC)
Max Loop Resistance 600 Ω (at 24VDC supply)
Operating Temperature 0°C to +55°C (+32°F to +131°F)
Power Consumption < 2.5 W (total module)
Dimensions (W×H×D) 25 × 160 × 120 mm (approx.)
Weight Approximately 0.2 kg

Functional Features:

  • Built-in 250 Ω precision resistor — no external resistor required
  • Per-channel linearization tables for direct transmitter type selection
  • Open-loop detection — alarm generated if transmitter wire breaks
  • Per-channel scaling configurable via FAST/TOOLS engineering station
  • Diagnostic data: Input value, deviation, alarm status transmitted to DCS
  • HART protocol compatible (pass-through for smart transmitter configuration)

Structure Characteristics:

  • DIN rail mountable within FAST/TOOLS I/O carrier
  • Spring-clamp terminal blocks for fast field wiring
  • LED indicators: Power (green), Alarm (red) per channel group
  • Backplane connector: 96-pin Eurocard-compatible edge connector

Applicable Industries:

  • Oil & Gas — Wellhead pressure and temperature monitoring
  • Chemical Processing — Reactor temperature and level measurement
  • Power Generation — Boiler drum level, steam flow
  • HVAC Systems — Chilled water temperature and flow
  • Food & Beverage — Tank level and temperature monitoring

Installation Requirements:

  • Mount in FAST/TOOLS compatible I/O carrier
  • Use shielded twisted-pair cable (22-18 AWG) for all transmitter connections
  • Ground shield at DCS end only to prevent ground loops
  • Maximum cable length: 1000 m (depending on wire gauge and loop resistance)
  • Loop power must be 24VDC ±10%

Usage Precautions:

  • Never apply external voltage to input terminals — use 2-wire transmitters only
  • Maximum loop resistance must not exceed 600 Ω at 24VDC
  • HART communication requires 250 Ω minimum loop resistance — built-in resistor satisfies this
  • Isolate inputs from high-voltage transients using signal conditioners when required
  • Calibrate annually or per site-specific maintenance schedule