Digital guide

You are here:

Yokogawa FC311-S1 AS-S9391AT-02

Product Category: Field-Mounted Flow Rate Converter / Totalizer

Product Overview:
The FC311-S1 is a compact flow rate converter designed for field mounting. The configuration AS-S9391AT-02 specifies: S1 = Single-channel input, AS = Analog/Pulse input type, S9391AT = Specific I/O card assignment, 02 = Revision code. It processes flow sensor signals and outputs standardized 4–20 mA and pulse signals.

Detailed content

Technical Specifications:

  • Input Signals: 4–20 mA DC, Pulse (contact closure), Frequency (0–10 kHz)
  • Output Signals: 4–20 mA DC, Pulse output, Relay output (alarm)
  • Power Supply: 24 VDC / 100–240 VAC (dual supply)
  • Accuracy: ±0.1% of reading
  • Display6-digit LED display (red, 14.2 mm digit height)
  • Communication: RS-485 (Modbus RTU protocol)
  • Pulse Input: Max 10 kHz, 5–24 VDC
  • Relay Output250 VAC 3 A / 30 VDC 3 A (SPDT)
  • Operating Temperature: -10°C to +55°C
  • Protection Rating: IP65 (NEMA 4X front panel)
  • Mounting: DIN rail / Wall mount / Pipe mount
  • Dimensions96 mm × 96 mm × 110 mm (W × H × D)

Functional Features:

  • Flow rate totalization (forward/reverse/net)
  • Instantaneous flow rate display on 6-digit LED
  • Analog output proportional to flow rate (4–20 mA)
  • Pulse output for remote totalizer
  • Relay alarm output (high/low flow alarm)
  • Modbus RTU communication for DCS/SCADA integration
  • Batch totalization with reset function
  • Zero cut function (eliminates low-flow noise)

Material Composition:

  • HousingDie-cast aluminum alloy with powder-coat finish
  • Front Panel: Polycarbonate with IP65 gasket seal
  • TerminalsPhosphor bronze, tin-plated screw terminals

Structural Characteristics:

  • Form Factor: Square 96×96 mm panel-mount housing
  • Depth: 110 mm (behind panel)
  • Weight: Approximately 700 g

Working Principle:
The FC311-S1 receives pulse, frequency, or 4–20 mA signals from a flow sensor (turbine, vortex, electromagnetic, etc.). The internal microprocessor calculates instantaneous flow rate and accumulated total using configurable K-factors and pipe dimensions. Results are output as 4–20 mA analog signal and pulse output, with alarm relay activation on setpoint violation.

Key Advantages:

  • IP65 front panel — suitable for harsh field environments
  • Multiple input types — compatible with virtually all flow sensors
  • Built-in totalizer eliminates need for separate totalizer
  • Modbus RTU enables seamless DCS integration
  • Compact 96×96 mm size saves panel space

Applicable Industries:

  • Oil & Gas (custody transfer, well monitoring)
  • Chemical Processing
  • Water & Wastewater
  • Power Generation (cooling water, steam)
  • Food & Beverage

Installation Requirements:

  • Mount in location with ambient temperature -10°C to +55°C
  • Use shielded cable for pulse input signals
  • Provide 24 VDC or 100–240 VAC power supply
  • For pipe mounting, use proper gasket and torque specifications

Usage Precautions:

  • Do not exceed maximum input frequency of 10 kHz
  • Verify K-factor and pipe size configuration matches actual sensor
  • Ensure proper grounding of signal cables
  • Do not disassemble in hazardous atmosphere