Product Overview:
The F3YP28-0P is an 8-channel analog input card for the CENTUM VP DCS platform, functionally similar to F3YP22-0P but with extended configuration options and enhanced diagnostics. It accepts 4-20 mA DC (2-wire) signals from field transmitters. The “0P” suffix indicates non-redundant (single) configuration. The “28” variant typically supports additional input range configurations compared to the “22” variant.

Detailed content

Technical Specifications:

  • Model Code: F3YP28-0P
  • Number of Channels: 8 channels
  • Input Signal: 4-20 mA DC (2-wire transmitter powered)
  • Input Impedance: 250 Ω (burden resistor built-in)
  • Resolution: 12-bit A/D converter (4096 steps)
  • Accuracy: ±0.1% of span
  • Scan Cycle: 1 second (all 8 channels)
  • Input Range Options (via jumper/configuration):
    • 0-20 mA
    • 4-20 mA
    • 0-10 mA
    • 1-5 V (with external resistor)
  • Isolation: Channel-to-channel isolation, 500 VDC
  • Power Supply: 5 VDC (from CENTUM VP I/O bus)
  • Power Consumption: ≤ 1.5 W
  • Operating Temperature Range: 0°C to +55°C
  • Storage Temperature Range: -20°C to +70°C
  • Relative Humidity: 5% to 95% RH (non-condensing)
  • MTBF: ≥ 80,000 hours
  • Dimensions (W × H × D): 25 mm × 160 mm × 165 mm
  • Weight: Approximately 250 g
  • Mounting Method: CENTUM VP I/O card cage (vertical insertion)

Functional Features:

  • Enhanced diagnostic capabilities compared to F3YP22: per-channel status LED, detailed error codes
  • Supports multiple input ranges configurable per channel via software
  • Burnout detection with configurable fail-safe output (3.6 mA, 21.6 mA, or hold last value)
  • Input filtering: Adjustable digital filter (0 to 10 seconds)
  • Zero/Span calibration via CS3000 configuration software (no potentiometer adjustment needed)
  • Hot-swap capable in compatible CENTUM VP I/O stations

Structural Features:

  • Standard F3-series card form factor (25 mm × 160 mm × 165 mm)
  • Front-panel LED indicators: PWR (green), RUN (green), ERR (red), CH1–CH8 (per channel)
  • Backplane connector: 96-pin eurocard connector for I/O bus interface
  • Terminal block: Screw-clamp type, 8-channel input terminals

Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Water/Wastewater, Chemical Processing, Food & Beverage, Mining

Installation Requirements:

  • Install in CENTUM VP I/O station (AIH or AOH cabinet)
  • Use shielded twisted-pair cable, AWG 22 to AWG 18
  • Maximum cable length: 1000 m (at 24 AWG)
  • Set correct input range in CS3000 system configuration for each channel

Precautions:

  • Do not exceed 25 mA input current — will damage A/D converter
  • Verify loop resistance ≤ 600 Ω including transmitter impedance
  • Do not connect voltage sources directly to current input terminals
  • Calibrate via software only — do not adjust on-card potentiometers