Yokogawa F3YP28-0P
Product Overview:
The F3YP28-0P is an 8-channel analog input card for the CENTUM VP DCS platform, functionally similar to F3YP22-0P but with extended configuration options and enhanced diagnostics. It accepts 4-20 mA DC (2-wire) signals from field transmitters. The “0P” suffix indicates non-redundant (single) configuration. The “28” variant typically supports additional input range configurations compared to the “22” variant.
Detailed content
Technical Specifications:
- Model Code: F3YP28-0P
- Number of Channels: 8 channels
- Input Signal: 4-20 mA DC (2-wire transmitter powered)
- Input Impedance: 250 Ω (burden resistor built-in)
- Resolution: 12-bit A/D converter (4096 steps)
- Accuracy: ±0.1% of span
- Scan Cycle: 1 second (all 8 channels)
- Input Range Options (via jumper/configuration):
- 0-20 mA
- 4-20 mA
- 0-10 mA
- 1-5 V (with external resistor)
- Isolation: Channel-to-channel isolation, 500 VDC
- Power Supply: 5 VDC (from CENTUM VP I/O bus)
- Power Consumption: ≤ 1.5 W
- Operating Temperature Range: 0°C to +55°C
- Storage Temperature Range: -20°C to +70°C
- Relative Humidity: 5% to 95% RH (non-condensing)
- MTBF: ≥ 80,000 hours
- Dimensions (W × H × D): 25 mm × 160 mm × 165 mm
- Weight: Approximately 250 g
- Mounting Method: CENTUM VP I/O card cage (vertical insertion)
Functional Features:
- Enhanced diagnostic capabilities compared to F3YP22: per-channel status LED, detailed error codes
- Supports multiple input ranges configurable per channel via software
- Burnout detection with configurable fail-safe output (3.6 mA, 21.6 mA, or hold last value)
- Input filtering: Adjustable digital filter (0 to 10 seconds)
- Zero/Span calibration via CS3000 configuration software (no potentiometer adjustment needed)
- Hot-swap capable in compatible CENTUM VP I/O stations
Structural Features:
- Standard F3-series card form factor (25 mm × 160 mm × 165 mm)
- Front-panel LED indicators: PWR (green), RUN (green), ERR (red), CH1–CH8 (per channel)
- Backplane connector: 96-pin eurocard connector for I/O bus interface
- Terminal block: Screw-clamp type, 8-channel input terminals
Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Water/Wastewater, Chemical Processing, Food & Beverage, Mining
Installation Requirements:
- Install in CENTUM VP I/O station (AIH or AOH cabinet)
- Use shielded twisted-pair cable, AWG 22 to AWG 18
- Maximum cable length: 1000 m (at 24 AWG)
- Set correct input range in CS3000 system configuration for each channel
Precautions:
- Do not exceed 25 mA input current — will damage A/D converter
- Verify loop resistance ≤ 600 Ω including transmitter impedance
- Do not connect voltage sources directly to current input terminals
- Calibrate via software only — do not adjust on-card potentiometers