Digital guide

You are here:

Yokogawa F3YP22-0P

Product Overview:
The F3YP22-0P is an 8-channel analog input card for the CENTUM VP Distributed Control System. It accepts 4-20 mA DC (2-wire) signals from field transmitters such as pressure transmitters, flow meters, level transmitters, and temperature transmitters. The “0P” suffix indicates non-redundant (single) configuration.

Detailed content

Technical Specifications:

  • Model Code: F3YP22-0P
  • Number of Channels: 8 channels
  • Input Signal: 4-20 mA DC (2-wire transmitter powered)
  • Input Impedance: 250 Ω (burden resistor built-in)
  • Resolution: 12-bit A/D converter (4096 steps)
  • Accuracy: ±0.1% of span
  • Scan Cycle: 1 second (all 8 channels)
  • Isolation: Channel-to-channel isolation, 500 VDC
  • Power Supply: 5 VDC (supplied from CENTUM VP I/O bus, no external power)
  • Power Consumption: ≤ 1.5 W
  • Operating Temperature Range: 0°C to +55°C
  • Storage Temperature Range: -20°C to +70°C
  • Relative Humidity: 5% to 95% RH (non-condensing)
  • MTBF: ≥ 80,000 hours
  • Dimensions (W × H × D): 25 mm × 160 mm × 165 mm (standard F3 card size)
  • Weight: Approximately 250 g
  • Mounting Method: CENTUM VP I/O card cage (vertical insertion)

Functional Features:

  • Accepts 2-wire loop-powered 4-20 mA transmitters (no external power needed)
  • Per-channel configuration via CS3000 system configuration software
  • Supports input filtering (adjustable deadband: 0 to 100% of span)
  • Burnout detection: Outputs fixed value (3.6 mA or 21.6 mA) on wire break
  • Live zero detection: Outputs fixed value on signal below 3.6 mA
  • Compatible with CENTUM VP HIS, ENG, OPR, and SVP stations

Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Water/Wastewater, Chemical Processing, Pulp & Paper, Mining

Installation Requirements:

  • Install in CENTUM VP I/O station (AIH or AOH cabinet)
  • Use shielded twisted-pair cable (AWG 22 to AWG 18) for 4-20 mA signals
  • Maximum cable length: 1000 m (at 24 AWG, depending on loop resistance)
  • Ensure loop resistance ≤ 600 Ω (including transmitter and wiring)

Precautions:

  • Do not apply voltage > 30 VDC across input terminals
  • Verify transmitter is 2-wire type before connection
  • Set correct input range in system configuration (e.g., 0-100°C, 0-10 bar)
  • Replace card only with Yokogawa F3YP22-0P or compatible equivalent

You may also like