Yokogawa F3YP22-0P
Product Overview:
The F3YP22-0P is an 8-channel analog input card for the CENTUM VP Distributed Control System. It accepts 4-20 mA DC (2-wire) signals from field transmitters such as pressure transmitters, flow meters, level transmitters, and temperature transmitters. The “0P” suffix indicates non-redundant (single) configuration.
Detailed content
Technical Specifications:
- Model Code: F3YP22-0P
- Number of Channels: 8 channels
- Input Signal: 4-20 mA DC (2-wire transmitter powered)
- Input Impedance: 250 Ω (burden resistor built-in)
- Resolution: 12-bit A/D converter (4096 steps)
- Accuracy: ±0.1% of span
- Scan Cycle: 1 second (all 8 channels)
- Isolation: Channel-to-channel isolation, 500 VDC
- Power Supply: 5 VDC (supplied from CENTUM VP I/O bus, no external power)
- Power Consumption: ≤ 1.5 W
- Operating Temperature Range: 0°C to +55°C
- Storage Temperature Range: -20°C to +70°C
- Relative Humidity: 5% to 95% RH (non-condensing)
- MTBF: ≥ 80,000 hours
- Dimensions (W × H × D): 25 mm × 160 mm × 165 mm (standard F3 card size)
- Weight: Approximately 250 g
- Mounting Method: CENTUM VP I/O card cage (vertical insertion)
Functional Features:
- Accepts 2-wire loop-powered 4-20 mA transmitters (no external power needed)
- Per-channel configuration via CS3000 system configuration software
- Supports input filtering (adjustable deadband: 0 to 100% of span)
- Burnout detection: Outputs fixed value (3.6 mA or 21.6 mA) on wire break
- Live zero detection: Outputs fixed value on signal below 3.6 mA
- Compatible with CENTUM VP HIS, ENG, OPR, and SVP stations
Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Water/Wastewater, Chemical Processing, Pulp & Paper, Mining
Installation Requirements:
- Install in CENTUM VP I/O station (AIH or AOH cabinet)
- Use shielded twisted-pair cable (AWG 22 to AWG 18) for 4-20 mA signals
- Maximum cable length: 1000 m (at 24 AWG, depending on loop resistance)
- Ensure loop resistance ≤ 600 Ω (including transmitter and wiring)
Precautions:
- Do not apply voltage > 30 VDC across input terminals
- Verify transmitter is 2-wire type before connection
- Set correct input range in system configuration (e.g., 0-100°C, 0-10 bar)
- Replace card only with Yokogawa F3YP22-0P or compatible equivalent