Yokogawa F3YP18-0N

Product Series: F3 I/O Series — CENTUM VP / CENTUM CS 3000 Distributed Control System

Product Overview:
The F3YP18-0N is a 16-point transistor (NPN) output module designed for the Yokogawa CENTUM VP and CENTUM CS 3000 DCS platforms. The 0N suffix indicates a non-redundant (single) configuration. This module provides discrete digital output signals for controlling solenoid valves, indicator lamps, relay coils, and other on/off field devices.

Detailed content

Technical Specifications:

Parameter Specification
Number of Channels 16 points
Output Type Transistor (NPN open-collector)
Output Voltage 24VDC (nominal), max 30VDC
Output Current 0.5 A per point (max), 50 mA per point (continuous)
On/Off Response Time < 1 ms (turn-ON), < 1 ms (turn-OFF)
Isolation Voltage 500 VAC (channel-to-channel, channel-to-backplane)
Insulation Resistance > 20 MΩ at 500VDC
Operating Temperature 0°C to +55°C (+32°F to +131°F)
Power Supply 5VDC (bus-powered from backplane)
Power Consumption < 4.0 W (total module)
Dimensions (W×H×D) 25 × 160 × 120 mm (approx.)
Weight Approximately 0.25 kg
Certifications CSA, FM, ATEX (when used with barrier)

Functional Features:

  • LED status indicators per channel (8 per group) for visual diagnostics
  • Group-wise diagnostic reporting via DCS operator station
  • Short-circuit protection on each output channel with auto-recovery
  • Backplane bus communication for fast data exchange with controller
  • Online insertion/removal (hot-swap) supported in CENTUM VP
  • Fail-safe default state configurable per channel (Open/Closed)

Material Composition:

  • Module housing: Flame-retardant PBT (Polybutylene Terephthalate) plastic, UL94 V-0 rated
  • PCBFR-4 glass epoxy with conformal coating
  • ConnectorsGold-plated pin connectors for reliable contact
  • Terminal blocksPhosphor bronze with tin plating

Applicable Industries:

  • Oil Refining — Valve position control, pump start/stop
  • Chemical Plants — Batch process sequencing
  • Power Plants — Auxiliary equipment control
  • Water Treatment — Pump and valve automation
  • Pulp & Paper — Conveyor and actuator control

Installation Requirements:

  • Install in F3 series compatible I/O station within CENTUM VP/CS 3000 rack
  • Use 24VDC loop power supply with adequate current capacity (≥ 8A for full load)
  • Maintain minimum 10 mm spacing between adjacent modules
  • Route output wiring in separate conduit from analog signal cables
  • Connect field device common (0V) to DCS common terminal

Usage Precautions:

  • Do not exceed 0.5 A per channel — use external relays for higher loads
  • Inductive loads require flyback diodes across solenoid coils
  • Verify output polarity (NPN) matches field device requirements
  • Replace module within 10 years of manufacture for reliability
  • Do not apply voltage to outputs when module is unpowered