YOKOGAWA F3YD32-1P
Product Series: F3 FA-M3R / F3 VP Series Programmable Logic Controller (PLC)
Product Introduction:
The F3YD32-1P is a 32-point analog output module for the Yokogawa F3 series PLC. It provides 16-bit resolution current output (4–20mA) for precise control of final control elements such as control valves, variable frequency drives (VFDs), and damper actuators. The 1P designation indicates 1-channel precision current output per module (32 channels total across the module).
Detailed content
Technical Specifications:
- Number of Output Channels: 32 channels (4–20mA DC)
- Output Type: 4–20mA DC (2-wire or 4-wire selectable per group)
- Resolution: 16-bit (1/65536 of full scale)
- Output Accuracy: ±0.1% of span (typical) / ±0.2% of span (maximum)
- Settling Time: ≤ 10 ms (to within ±0.1% of final value)
- Update Rate: 1 ms per channel (all 32 channels updated simultaneously)
- Load Resistance: Maximum 600 Ω (at 24 VDC supply)
- Isolation: Channel-to-channel isolation via photocouplers
- Backplane Isolation: 500 VAC (1 minute)
- Power Supply: 5 VDC from F3 backplane bus
- Power Consumption: Approximately 3.0 W (from backplane)
- Operating Temperature: 0 to +55 °C (32 to 131 °F)
- Dimensions: W 98 mm × H 120 mm × D 80 mm (approximate)
- Weight: Approximately 180 g
Functional Features:
- 16-bit D/A conversion — high-resolution analog output
- Individual channel calibration — zero and span adjustment per channel
- Output hold on communication failure — last value retention
- Group-wise output update — configurable update timing
- Fault detection — open-circuit and short-circuit detection per channel
- Compatible with F3CPU-B, F3CPU-S, F3CPU-R main units
Performance Parameters:
- Linearity: ±0.05% of span (typical)
- Temperature Coefficient: ±0.005% of span per °C
- Cross-talk: ≤ -80 dB (between adjacent channels)
- Common Mode Rejection Ratio (CMRR): ≥ 80 dB
Structural Features:
- Module format: Standard F3 series base-mounted module
- Connector: 40-pin connector (backplane interface)
- Terminal block: Screw terminal for field wiring (output side)
- Housing material: Flame-retardant ABS resin (UL94 V-0)
- LED indicators: Per-channel status LEDs (output active, fault)
Applicable Industries:
- Oil & Gas — Control valve positioning, VFD speed control
- Chemical & Petrochemical — Precise flow and pressure control
- Power Generation — Boiler damper control, feedwater regulation
- Water & Wastewater — Pump speed control, chemical dosing
- Pulp & Paper — Basis weight control, consistency control
Installation Requirements:
- Mount on F3 series main rack (F3B-20HR or equivalent)
- Use shielded twisted-pair cable for all analog output wiring
- Maximum cable length: 200 m (for 4–20mA, with shielded cable)
- Ensure loop power supply voltage ≥ 18 VDC (accounting for load resistance)
- Ground the cable shield at controller end only
Precautions:
- Do not exceed 24 mA per channel — will damage output circuit
- Do not apply voltage > 30 VDC across any output terminal
- Calibrate all channels during initial commissioning and annually thereafter
- Do not hot-swap the module — power down the PLC before insertion/removal