Yokogawa EB501-10
Technical Specifications:
- Communication bus: Compatible with Yokogawa’s proprietary ESB bus, supporting dual redundancy configuration.
- Number of communication ports: 2, supporting redundant connection.
- Data transmission rate: 100Mbps (full-duplex).
- Working voltage: 24V DC, current consumption ≤ 500mA.
- Working temperature: -20~70°C.
- Isolation: Bus and system isolation voltage 1.5kV AC for 1 minute.
Detailed content
- Functional Characteristics:
- It supports dual redundancy communication, which improves the reliability and availability of the system.
- It has a self-diagnosis function, which can monitor the communication status in real time and alarm when a fault occurs.
- It is plug-and-play, easy to install and replace, and reduces maintenance time.
- It is highly compatible and can work seamlessly with various I/O modules of the CENTUM VP system.
- Application Scenarios: It is applied in the DCS system of process industries such as petroleum chemical industry, chemical industry, and power plant, and is used to connect the I/O rack and the main control station to realize the data transmission of process control signals, ensuring the real-time and reliability of industrial process monitoring and control.