  • Product Introduction: A 16-channel analog input module for Yokogawa’s S2 I/O system, designed for high-precision measurement of process variables with HART communication capability for smart sensor integration.
  • Technical Specifications:
    • Number of Channels: 16 differential channels
    • Input Signal: 4-20mA DC, HART protocol compatible
    • Measurement Accuracy: ±0.04% of full scale
    • Sampling Rate: 10 ms per channel

Detailed content

    • Isolation: Channel-to-channel 500V AC, channel-to-backplane 1500V AC
    • Power Supply: 24V DC, 3W power consumption
    • Operating Temperature: -20 to 70°C
    • Weight: 0.4 kg
  • Functional Features:
    • HART communication for remote sensor configuration and diagnostics
    • High precision measurement for accurate process monitoring
    • Channel-wise configuration for mixed input types
    • Built-in surge protection for harsh industrial environments
    • Easy integration with Yokogawa’s CENTUM VP DCS
  • Application Scenarios: Chemical processing, water treatment, and manufacturing lines for monitoring pressure, flow, temperature, and level parameters using smart HART-enabled sensors.