Product Introduction: A high-density, 16-channel analog input module for Yokogawa CENTUM VP DCS, paired with the ATA4S-00 pressure-clamp terminal block. It accepts 4–20 mA DC signals from field transmitters, providing reliable data acquisition for process control.

Technical Specifications

  • Input Channels: 16 non-isolated channels
  • Input Signal: 4–20 mA DC

Detailed content

  • Input Impedance: 250 Ω
  • Accuracy: ±0.1% of full scale
  • Conversion Time: 10 ms
  • Redundancy: Supports dual-redundant configuration
  • Terminal Block: ATA4S-00 pressure-clamp type for secure connections
  • Power Supply: 24 V DC
  • Operating Temperature: -20°C to +60°C

    Key Features

  • High-Density I/O: 16 channels in a single module for efficient space utilization.
  • Fast Conversion: 10 ms response time for dynamic process control.
  • Burnout Detection: Automatically detects transmitter failures and triggers alarms.
  • Redundancy Support: Improves system availability with dual-module configuration.
  • Secure Wiring: ATA4S-00 terminal block ensures reliable, maintenance-free connections.
  • Input Filtering: Built-in filter reduces electrical noise from field signals.
  • Seamless DCS Integration: Direct compatibility with CENTUM VP control architecture.

    Applications

  • Multi-point process monitoring in large-scale chemical plants.
  • Flow, level, and pressure measurement in power generation facilities.
  • Data acquisition for closed-loop control systems in manufacturing.
  • Integration with PLCs and SCADA systems for comprehensive plant monitoring.
  • Quality control parameter monitoring in food and beverage production.