Digital guide

You are here:

Yokogawa AAI135‑H

  • Product Name: Analog Input Module (Current Input, Isolated)
  • Product Series: Centum VP / Centum CS 3000 Series I/O Modules
  • Technical Specifications:
    • Input Signal: 4–20 mA DC analog current input
    • Isolation: Galvanic isolation between field side and control system side

Detailed content

    • Resolution: 16‑bit high‑precision A/D conversion
    • Power Supply: 24 V DC nominal operating voltage
    • Operating Temperature Range: 0 °C to +55 °C
    • Storage Temperature Range: -40 °C to +85 °C
  • Functional Features: Multi‑channel analog signal acquisition, signal isolation protection, noise suppression, real‑time data transmission to DCS controller
  • Performance Parameters: Input impedance ≥1 MΩ, conversion accuracy ±0.1% full scale
  • Material Composition: Industrial‑grade flame‑retardant PCB, aluminum alloy heat dissipation shell, anti‑corrosion terminal block
  • Structural Characteristics: Plug‑in modular structure, standard rack‑mount installation, hot‑swap support
  • Working Principle: Collect field analog current signals, convert analog signals to digital signals via high‑precision A/D chip, transmit processed digital data to the main control unit
  • Advantages & Highlights: High isolation performance, strong anti‑interference capability, high measurement precision, stable long‑term operation
  • Applicable Industries: Petrochemical, power generation, pharmaceutical, water treatment, metallurgy
  • Installation Requirements: Install in Class I industrial control cabinet, vertical mounting, maintain ≥20 mm heat dissipation gap between adjacent modules
  • Usage Precautions: Strictly follow 24 V DC power polarity; avoid high‑voltage surge impact; regular calibration every 12 months