Yokogawa 915U-2-900US
Product Overview:
The 915U-2-900US is a battery backup unit (BBU) for the CENTUM VP DCS system. It provides uninterrupted 24 VDC power to critical DCS components (CPU, I/O cards, communication modules) during AC mains power failure. The model code breakdown: 915U = battery backup series, 2 = 2-slot unit, 900 = 900 mAh capacity, US = United States specification (120 VAC input).
Detailed content
Technical Specifications:
- Model Code: 915U-2-900US
- Type: Sealed Lead-Acid (SLA) Battery Backup Unit
- Number of Battery Slots: 2 slots
- Battery Type: Sealed Lead-Acid (maintenance-free, VRLA)
- Battery Capacity: 900 mAh (per battery, 12 V)
- Output Voltage: 24 VDC (nominal)
- Output Current: 900 mA (maximum continuous discharge)
- Backup Duration: Approximately 30 minutes at full load (900 mA)
- Charging Voltage: 27.6 VDC (float charge), 28.8 VDC (boost charge)
- Charging Current: 90 mA (trickle charge, continuous)
- Input Voltage: 120 VAC (US specification), 60 Hz
- Power Consumption (Charging Mode): ≤ 5 W
- Operating Temperature Range: 0°C to +55°C
- Storage Temperature Range: -20°C to +70°C
- Relative Humidity: 5% to 95% RH (non-condensing)
- Battery Life: 5 years (typical, at 25°C ambient)
- Recharge Time: ≤ 8 hours (from fully discharged)
- MTBF: ≥ 50,000 hours
- Dimensions (W × H × D): 25 mm × 90 mm × 100 mm (approx.)
- Weight: Approximately 800 g (with batteries installed)
- Mounting Method: DIN rail (35 mm) mounting inside DCS cabinet
Functional Features:
- Provides automatic switchover from AC mains to battery on power failure (transfer time: < 10 ms)
- Automatic recharge when AC mains is restored
- LED indicators: CHARGE (green), BATTERY (green), ALARM (red)
- Low battery alarm output to DCS (dry contact, NO/NC)
- Battery test button for periodic capacity verification
- Supports hot-swap battery replacement (with DCS in operation)
- Compatible with CENTUM VP CPU cards (FCU, FCIU, etc.)
Structural Features:
- DIN rail-mountable metal/plastic housing
- Battery compartment with hinged cover for easy battery access
- Terminal block for 24 VDC output and alarm contact
- Ventilation slots for heat dissipation during charging
Material Composition:
- Housing: ABS resin (UL94 V-0)
- Battery: Lead-acid, VRLA, ABS case
- Terminals: Brass, nickel-plated
- Internal wiring: Silicone-insulated wire, 105°C rated
Applicable Industries:
Oil & Gas, Petrochemical, Power Generation, Water/Wastewater, Chemical Processing — any facility using CENTUM VP DCS requiring uninterrupted operation
Installation Requirements:
- Install on 35 mm DIN rail inside CENTUM VP CPU cabinet
- Connect 120 VAC input with dedicated circuit breaker (rated 1 A)
- Connect 24 VDC output to DCS power bus terminals
- Install battery alarm contact to DCS digital input for monitoring
- Replace batteries every 5 years or when capacity drops below 80%
Precautions:
- Do not install in environments exceeding 55°C — reduces battery life
- Do not short-circuit battery terminals — risk of fire
- Do not dispose of batteries in regular trash — recycle as hazardous waste (lead-acid)
- Verify battery voltage ≥ 24 VDC before connecting to DCS
- Perform battery load test quarterly using test button
- Do not mix old and new batteries in the same unit