Digital guide

You are here:

Honeywell FC-HON32-23A32

Product Name:​ OneWireless™ Field Device Access Point (FDAP32) — Industrial Wireless Mesh Access Point
Product Introduction:​ Based on the available Honeywell product documentation, the FC-HON32-23A32 corresponds to the Honeywell OneWireless™ FDAP32 — an industrial meshing access point for ISA100™ Wireless (IEC 62734) and WirelessHART® (IEC 62591) field instruments. The FDAP32 is rated for hazardous plant environments (Class I, Div. 2 / Zone 2) and auto-discovers neighboring wireless devices to form a secure IEEE 802.15.4 mesh network.

Detailed content

Technical Specifications:
  • Wireless protocols: ISA100 Wireless (IEC 62734), WirelessHART (IEC 62591)
  • Frequency band: 2.4 to 2.483 GHz (ISM band)
  • Transmit power: Max 18 dBm
  • Receiver sensitivity: -100 dBm @ 250 Kbps
  • Data rates: ISA100 250 Kbps (DSSS/O-QPSK); BLE 1 Mbps (FHSS/FSK); Wired 10/100 Mbps
  • Encryption: AES 128-bit
  • Authentication: Over-the-air and BLE-based; WirelessHART HART modem only
  • Network hops: 4 hops
  • Antenna ports: 2× external 2.4 GHz antenna ports (antenna diversity for multi-path reliability)
  • Ethernet: 1× 10/100 Mbps Ethernet port (auto-negotiation)
  • Supported Enraf FlexLine Radar Gauges / WFI: Up to 40
  • Power: 18–30 VDC at 2 W; or Power over Ethernet (PoE) at 5 W
  • Operating temperature: -40 °C to +70 °C (IECEx, ATEX, CSA)
  • Humidity: 0–95% RH, non-condensing
  • Ingress protection: IP66 / IP67
  • Corrosion resistance: G3 per ANSI/ISA-S71.04-1985
  • Shock: 15 G non-operational; 4–5 G operational
  • Dimensions: 290 × 281 × 173 mm (11.4 × 11.1 × 6.8 in)
  • Weight: 2 kg (4.6 lb)
  • Hazardous location rating: Class I, Div. 2, Groups A/B/C/D; Zone 2; T4
  • Standards: CE, CSA, ETSI, FCC, IC, IEC 61326-1
Functional Features:
  • Self-forming, self-healing IEEE 802.15.4 mesh network
  • Dual external antenna ports with antenna diversity for enhanced reliability in multi-path indoor/outdoor environments
  • Supports all ISA100 Wireless and WirelessHART field instruments, including wired HART instruments connected via wireless adapters
  • Enables critical monitoring and open-loop control in hazardous environments requiring update rates < 10 seconds
  • AES 128-bit encryption with over-the-air and BLE-based authentication
  • Auto-discovery of neighboring FDAPs, ISA100 Wireless, and WirelessHART field instruments
Application Scenarios:​ Implementation of wireless field instrument networks in harsh, hazardous plant environments — including oil & gas production, chemical processing, refining, and utilities — where updating rates of less than 10 seconds are acceptable for critical monitoring or open-loop control. The FDAP32 supports up to 40 Enraf FlexLine radar gauges or Wireless Field Instruments.
Structural & Material Characteristics:​ The FDAP32 is housed in a ruggedized enclosure rated IP66/IP67 with G3 corrosion-resistant materials per ISA-S71.04. It features two external antenna ports for 2.4 GHz antennas, one 10/100 Mbps Ethernet port, and a grounding cable connection. The unit weighs 2 kg and measures 290 × 281 × 173 mm.
Working Principle:​ The FDAP32 operates as a mesh node in a OneWireless network. It communicates with ISA100 Wireless and WirelessHART field instruments over the 2.4 GHz ISM band using IEEE 802.15.4 radio links. Incoming wireless data is encrypted (AES 128-bit), authenticated, and forwarded via the 10/100 Mbps Ethernet port to the host system. The device auto-discovers neighbors and dynamically forms a self-healing mesh with up to 4 network hops.
Installation Requirements:
  • Mount in accordance with Class I, Div. 2 / Zone 2 hazardous-location regulations
  • Provide 18–30 VDC power (2 W) or PoE (5 W)
  • Connect both external antennas for antenna diversity
  • Ground the unit via the provided grounding cable
  • Ensure Ethernet cable routing complies with plant network infrastructure
  • Operating temperature range: -40 °C to +70 °C
Usage Notes:
  • The “23A32” suffix specifics (e.g., antenna configuration, regional certification package) were not individually detailed in the publicly retrieved Honeywell documentation; consult the official Honeywell OneWireless FDAP datasheet for the exact variant configuration.
  • Do NOT exceed 30 VDC input power
  • Maintain antenna clearance from metal obstructions for optimal RF propagation
  • Periodically verify mesh network health and neighbor tables