Digital guide

You are here:

Honeywell CC-TAID01

Product Name:​ Honeywell CC-TAON01 (Part No. 51306519-175 Rev. B) Analog Output IOTA PWA Module
Product Introduction:​ The CC-TAON01 is a highly reliable analog output module mounted on an IOTA base, specifically designed for DCS and PLC networks. It receives digital commands from the controller and converts signals to standard current (0–20 mA, 4–20 mA) or voltage (0–10 V, ±10 V) outputs for driving valves, actuators, and other field devices.

Detailed content

Technical Specifications:
  • Part Number: 51306519-175 Rev. B
  • Module Type: 8-channel Analog Output IOTA PWA
  • Output Channels: 8 independent channels
  • Output Ranges: 0–20 mA, 4–20 mA, 0–10 V, ±10 V (selectable)
  • D/A Resolution: 16-bit
  • Accuracy: ±0.05% F.S. (typical)
  • Temperature Drift: ≤ 20 ppm/°C
  • Response Time: ≤ 10 ms
  • Isolation Voltage: ≥ 1500 VAC between channels and to backplane
  • Interface: IOTA base dedicated backplane bus
  • Power Supply: 5 V DC (provided by base backplane)
  • Power Consumption: ≤ 4 W
  • PCB: 6-layer industrial-grade multilayer board
  • Operating Temperature: -40 °C to +70 °C
  • Storage Temperature: -40 °C to +85 °C
  • Relative Humidity: 5% to 95%, non-condensing
  • Installation: Plug-in card type, supports hot-swapping
  • Indicators: Power (green), Output Activity (blue), Fault (red)
Functional Features:​ High-precision output with Rev. B firmware optimizing linearization algorithm and temperature drift compensation; multi-range support (current/voltage dual mode switchable); anti-interference design with channel isolation and EMI filtering; hot-swap maintenance for continuous production; in the Experion PKS C Series context, it provides 8 channels of 4–20 mA DC output with HART communication support, typical accuracy of ±0.1% of span, 16-bit resolution, channel-to-channel and channel-to-bus photoelectric isolation, and comprehensive diagnostics (module status, communication status, output loop open-circuit detection, output value over-limit alarm).
Application Scenarios:​ Acts as the “command executor” in Honeywell Experion PKS DCS architecture, driving valves and actuators in process control applications.
Performance Parameters:​ Output error less than ±0.05% F.S.; response time less than 10 ms; load capacity typically up to 1050 Ω (at 24 VDC supply) in the Experion PKS C Series implementation.
Material Composition:​ 6-layer industrial-grade multilayer PCB with channel isolation and EMI filtering components.
Structural Features:​ Plug-in card design mounted on C-Series I/O module carrier; supports hot-swapping (when allowed by system configuration); LED indicators for status, communication, and fault.
Working Principle:​ Receives digital commands from controller, converts via 16-bit D/A converter to selectable current/voltage outputs; Rev. B firmware optimizes linearization and temperature drift compensation; provides channel-to-channel and channel-to-backplane isolation; detects output loop open-circuit and over-limit conditions.
Installation Requirements:​ Plug-in installation on C-Series I/O module carrier/IOTA base; 5 VDC power provided by backplane; supports hot-swapping when permitted by system configuration.
Usage Precautions:​ Monitor LED indicators for power, output activity, and fault conditions; ensure proper output loop wiring to avoid open-circuit; configure fail-safe behavior appropriately; regular maintenance checks for optimal performance.