Digital guide

You are here:

Honeywell 8C-PAONA1

Product Name:​ Series 8 16-Channel 4–20 mA Analog Output Module (Non-HART, G3 coated)
Product Introduction:​ The 8C-PAONA1 (part number 51454469-175) is a high-precision 16-channel analog output module in the Experion PKS Series 8 I/O architecture. It converts the C300 controller’s digital control algorithms into accurate 4–20 mA analog signals to drive final control elements such as valve positioners, variable-speed drives, and dampers. This “175” variant carries factory G3 conformal coating for corrosive-atmosphere protection.

Detailed content

Technical Specifications:
  • Module type: Analog Output (Non-HART)
  • Output channels: 16
  • Output type: 4–20 mA DC
  • Directly settable output current range: 2.9 mA to 21.1 mA
  • Maximum output compliant voltage (@ 24 V supply, 22–28 VDC): 16 V
  • Maximum open-circuit voltage: 22 V
  • Load resistance (@ 24 V supply): 50–800 Ω
  • Resolution: ±0.05% of full scale (nominal)
  • Linearity: ±0.05% of full scale (nominal)
  • Calibrated accuracy: ±0.2% of full scale at 25 °C
  • Output ripple: < 100 mV peak-to-peak at power-line frequency across 250 Ω load
  • Output temperature drift: 0.005% of full scale / °C
  • Module voltage: 24 VDC
  • Module current: 190 mA
  • Maximum power consumption: 5.8 W
  • Response time (DAC input code to output settling within 1%): 80 ms
  • Redundancy switchover gap: 10 ms maximum
  • Hot-swap (RIUP): Supported
  • Operating temperature: -40 °C to +70 °C
  • G3 conformal coated (resists H₂S, Cl₂, ammonia per ISA S71.04)
  • Weight: 0.45 kg; Dimensions: 152 × 98 × 42 mm
Functional Features:
  • Extensive self-diagnostics
  • Optional redundancy for bumpless switchover
  • Per-channel configurable FAILOPT (safe-state) behavior — output can be directed to hold last value or shed to a user-defined safe value
  • Galvanic isolation between field wiring and internal system bus
  • Streamlined non-HART signal path for cost-effective standard 4–20 mA loops
  • Slim vertical form factor for natural-convection cooling in high-density cabinets
Application Scenarios:​ Driving analog final-control elements in continuous process industries — valve positioners, damper actuators, variable-speed drives, and recording/indicating devices — particularly in chemically aggressive atmospheres requiring G3 corrosion protection.
Structural & Material Characteristics:​ The module is built on a coated PCB housed in the Series 8 slim vertical form factor. It integrates D/A conversion, galvanic isolation, and per-channel safe-state logic. It mates with a Series 8 IOTA which provides field wiring termination and redundant I/O Link connectivity.
Working Principle:​ The C300 controller sends digital output codes over the I/O Link. The module’s D/A converter translates each code into a proportional 4–20 mA current. Onboard circuitry regulates the current through the field load (50–800 Ω), maintaining the setpoint against varying load resistance up to the 16 V compliant voltage limit. Self-diagnostics continuously monitor each channel’s integrity.
Installation Requirements:
  • Mount on a compatible Series 8 AO IOTA (redundant IOTA recommended for high-availability applications)
  • Provide 24 VDC system power via the IOTA bus
  • For redundant operation, install a second 8C-PAONA1 on the same IOTA
  • Verify the load resistance of each field device falls within 50–800 Ω at the supplied voltage
Usage Notes:
  • This module is NON-HART. “Smart” valve positioners will still respond to the 4–20 mA signal, but the DCS cannot read HART digital diagnostics. For HART capability, use the 8C-PAOHA1 which is backward-compatible on the same IOTA (module configuration in Experion Control Builder must be updated).
  • Do not exceed 22 V open-circuit or 16 V compliant voltage
  • Hot-swap is supported, but confirm redundancy status before extracting a module in an active control loop