Emerson 1410S2AA32AD4N7RD
Product Name: Rosemount 1410S2 Outdoor WirelessHART Gateway
Overview: This gateway aggregates WirelessHART field instrument data and converts it to wired Ethernet for DCS, PLC and asset-system integration. The S2 outdoor configuration uses a low-copper aluminum housing with polyurethane coating for harsh outdoor installations and pairs with the 781S smart antenna.
Detailed content
Technical Specifications: Wireless protocol is WirelessHART per IEC 62591; operating band is 2.4 to 2.5 GHz DSSS. Standard network capacity is 200 devices, with large-capacity options supporting 500 devices. Update rates include 1, 2, 4, 8, 16 and 32 seconds plus 1 to 60 minutes. Ethernet security includes TLS encryption and role-based access control. Housing protection is IP66. Operating temperature is -40 to +65 °C. Power and data use industrial Ethernet; mounting supports pipe and DIN rail. Weight is approximately 1.25 kg. Dimensions are approximately 15.9 cm x 22.4 cm x 6.4 cm.
Functional Features: Self-organizing WirelessHART mesh, automatic path redundancy, high device capacity, outdoor IP66 enclosure, encrypted Ethernet uplink, local configuration through DIP switches and LED indicators, direct compatibility with Rosemount WirelessHART transmitters and 781S antenna.
Application Scenarios: Oil and gas wellheads and pipelines, chemical plants, power generation auxiliary systems, water and wastewater treatment, outdoor temperature/pressure/vibration/level wireless monitoring, hazardous-area sensor networks requiring Ethernet integration.
Materials and Structure: Enclosure is low-copper aluminum with polyurethane coating; antenna port interfaces with 781S smart antenna; internal radio, security processor and Ethernet PHY are mounted on industrial control boards; gasket seals maintain IP66.
Working Principle: Field WirelessHART instruments transmit process data to the 781S antenna and 1410S2 radio. The gateway performs mesh routing, data aggregation and protocol conversion to TCP/IP Ethernet. Encrypted Ethernet frames are delivered to the control system; DIP and LED provide local network status and commissioning feedback.
Installation Requirements: Mount on pipe or 35 mm DIN rail with clear antenna clearance. Install 781S antenna per Emerson orientation rules. Provide shielded industrial Ethernet cable, Cat5 or better, with properly terminated RJ45 or fiber converter as required. Configure network ID, security key, IP address and device update rate before placing instruments online.
Usage Precautions: Verify operating temperature before outdoor installation. Keep antenna feeders away from high-power RF sources. Use only approved low-copper aluminum-compatible mounting hardware in corrosive areas. Perform annual radio diagnostics and replace antenna seals if IP66 integrity is reduced.