Product Name​
High-Precision Analog Input Module
Product Introduction​
Signal acquisition module for ABB AC800M control systems. Designed for accurate measurement of temperature, pressure, flow, and other process variables from field instruments.

Detailed content

Technical Specifications​
  • Channels: 16 differential analog inputs
  • Voltage Input: ±10 V, ±5 V, ±1 V, 0–10 V
  • Current Input: 0–20 mA, 4–20 mA
  • RTD Input: Pt100, Pt1000, 2/3/4-wire
  • Thermocouple Input: J, K, T, E, R, S, N types
  • Resolution: 16 bits plus sign
  • Accuracy: ±0.05% full scale at 25 °C
  • Sampling Rate: 10 scans per second for all channels
  • Common Mode Rejection: >120 dB at 50/60 Hz
  • Channel Isolation: 500 V DC channel-to-channel, 1000 V DC to backplane
  • HART Support: Optional through HART modem
Functional Features​
  • Multi-signal software configuration
  • Automatic cold-junction compensation
  • Programmable low-pass filtering
  • Open-wire detection for current inputs
  • Range overrun alarm
  • Hot-swapping in redundant configurations
Application Scenarios​
  • Process temperature monitoring
  • Pressure and flow measurement
  • Power plant instrumentation
  • Chemical reactor control
  • Water treatment and metallurgy systems
Structural Characteristics​
  • Metal industrial module housing
  • IP20 protection
  • Vertical installation on S800 I/O base
  • Removable spring-terminal connectors
  • Integrated diagnostic LEDs
Working Principle​
Each input channel conditions the field signal, converts it through a high-resolution ADC, and transfers isolated digital data to the AC800M controller through the I/O bus.
Installation Requirements​
  • Mount in grounded control cabinet
  • Use shielded twisted-pair instrument cables
  • Connect shield to designated ground terminal
  • Verify base unit and firmware compatibility
  • Configure signal type in engineering software
Usage Precautions​
  • Do not connect unknown signal types before configuration
  • Avoid shared grounds between channels
  • Perform cold-junction compensation calibration periodically
  • Replace only with identical or approved module version