Technical Specifications
- Channels: 16 differential analog inputs
- Voltage Input: ±10 V, ±5 V, ±1 V, 0–10 V
- Current Input: 0–20 mA, 4–20 mA
- RTD Input: Pt100, Pt1000, 2/3/4-wire
- Thermocouple Input: J, K, T, E, R, S, N types
- Resolution: 16 bits plus sign
- Accuracy: ±0.05% full scale at 25 °C
- Sampling Rate: 10 scans per second for all channels
- Common Mode Rejection: >120 dB at 50/60 Hz
- Channel Isolation: 500 V DC channel-to-channel, 1000 V DC to backplane
- HART Support: Optional through HART modem
Functional Features
- Multi-signal software configuration
- Automatic cold-junction compensation
- Programmable low-pass filtering
- Open-wire detection for current inputs
- Range overrun alarm
- Hot-swapping in redundant configurations
Application Scenarios
- Process temperature monitoring
- Pressure and flow measurement
- Power plant instrumentation
- Chemical reactor control
- Water treatment and metallurgy systems
Structural Characteristics
- Metal industrial module housing
- IP20 protection
- Vertical installation on S800 I/O base
- Removable spring-terminal connectors
- Integrated diagnostic LEDs
Working Principle
Each input channel conditions the field signal, converts it through a high-resolution ADC, and transfers isolated digital data to the AC800M controller through the I/O bus.
Installation Requirements
- Mount in grounded control cabinet
- Use shielded twisted-pair instrument cables
- Connect shield to designated ground terminal
- Verify base unit and firmware compatibility
- Configure signal type in engineering software
Usage Precautions
- Do not connect unknown signal types before configuration
- Avoid shared grounds between channels
- Perform cold-junction compensation calibration periodically
- Replace only with identical or approved module version