B&R X20BM33
Product Series: B&R X20 I/O System (X20BM Series)
Product Introduction: The X20BM33 is a 3-channel digital output module with transistor (NPN sink) outputs for the B&R X20 distributed I/O architecture. It is designed for applications requiring a small number of controlled DC output channels with fast response and high reliability.
Detailed content
Technical Specifications:
- Number of Channels: 3 digital outputs
- Output Type: Transistor (NPN / Sink)
- Output Voltage: 24V DC
- Maximum Output Current per Channel: 0.5 A
- Total Module Current: 1.5 A (aggregated)
- Response Time (ON→OFF / OFF→ON): < 1 ms (typical)
- Isolation: Channel-to-channel isolation, group-to-group isolation
- Rated Insulation Voltage: 500 V AC (IEC 61131-2)
- Supply Voltage: 24V DC via X20 bus connector
- Power Consumption: Approx. 1.0 W
Functional Features:
- Per-channel wire-break and short-circuit diagnostics
- Individual LED status indicator per channel
- Spring-loaded push-in terminal technology
- Hot-swap capable
- Integrated overcurrent protection per channel
- Reverse polarity protection on power supply input
Structural Features:
- Form Factor: Compact slim-line, 45 mm width
- Mounting: DIN rail (35 mm TS 35) / direct screw mounting
- Connector: X20 system bus connector (top side)
- Terminal Type: Push-in spring clamp, 0.14 mm² to 2.5 mm²
- Housing Material: Polycarbonate (PC), UL94 V-0
- Protection Rating: IP20
- Dimensions (W × H × D): 45 mm × 90 mm × 75 mm (approx.)
- Weight: Approx. 100 g
Operating Conditions:
- Operating Temperature: -25°C to +70°C
- Storage Temperature: -40°C to +85°C
- Relative Humidity: 5% to 95% (non-condensing)
- Vibration: 5 m/s² (IEC 60068-2-6)
- Shock: 30 g (IEC 60068-2-27)
Applicable Industries:
- Small-scale machine automation
- Pick-and-place systems
- Valve and solenoid control
- Indicator light / signal lamp control
- Safety relay output replacement
Installation Requirements:
- DIN rail 35 mm (EN 60715)
- Minimum 10 mm spacing for ventilation
- Wire size: 0.14–2.5 mm² copper conductors
- Polarity: 24V DC to load, output sinks to 0V common
Usage Precautions:
- Maximum per-channel current: 0.5 A — do not exceed
- Inductive loads require external suppression diodes
- Do not apply AC voltage to transistor outputs
- Ensure correct 24V DC common (0V) connection
Advantages & Highlights:
- Ultra-compact 3-channel design saves cabinet space
- Sub-1ms switching for fast actuator control
- Full diagnostic capability per channel
- Tool-free push-in wiring