B&R 7AI354.7
Product Type: Analog Input Module
Model Number: 7AI354.7
Product Introduction:
The B&R 7AI354.7 is a 4-channel analog input module from the X20 series. It acquires analog signals from sensors, transmitters, and process instruments and converts them into digital values for the B&R controller. The module supports both voltage and current input signals with high accuracy.
Detailed content
Technical Specifications:
- Number of Channels: 4
- Input Signal Type: 0 to 10 V DC / 0 to 20 mA / 4 to 20 mA (selectable per channel)
- Resolution: 12-bit (4096 steps)
- Input Impedance (Voltage Mode): ≥ 100 kΩ
- Input Impedance (Current Mode): 250 Ω (for 0-20 mA) / 125 Ω (for 4-20 mA)
- Accuracy: ±0.1% of full scale
- Conversion Time: ≤ 1 ms per channel
- Supply Voltage: 24 V DC (nominal), range 20.4 V to 28.8 V
- Power Consumption: ≤ 2.0 W
- Isolation: Channel-to-channel galvanic isolation, 500 V DC
- Isolation to Bus: 500 V DC
- Operating Temperature: 0 °C to +55 °C
- Storage Temperature: -25 °C to +70 °C
- Relative Humidity: 5% to 95% (non-condensing)
- Dimensions (W x H x D): 22.5 mm x 120 mm x 79.5 mm
- Weight: Approximately 150 g
Functional Features:
- Independent configuration per channel (voltage or current)
- 12-bit A/D conversion with high linearity
- Overvoltage protection on each input (up to 30 V DC)
- Reverse polarity protection on current inputs
- Diagnostic LED per channel
- Integrated filter for noise suppression
- Fully compatible with B&R Automation Studio
Structural Characteristics:
- DIN rail mounting (TS 35)
- Spring-loaded plug-in terminal connectors
- ABS plastic housing with high mechanical strength
- Front-facing LED status indicators
- X20 bus connector on bottom edge
Working Principle:
Analog signals from field sensors enter the module through protected input terminals. Each channel passes through an input protection circuit (overvoltage and reverse polarity protection). A multiplexer routes the selected channel to a 12-bit successive approximation ADC. The digital result is transferred to the controller via the X20 bus. Channel isolation is maintained via optocouplers.
Advantages & Highlights:
- 4 independent channels with per-channel configuration flexibility
- 12-bit resolution delivers high measurement precision
- Robust input protection guards against field wiring errors
- Galvanic isolation ensures noise-free signal acquisition
- Hot-swap capability in X20 systems
Applicable Industries:
- Chemical and petrochemical plants
- Water and wastewater treatment
- HVAC systems
- Process control in food industry
- Pharmaceutical manufacturing
- Energy management systems
Installation Requirements:
- Mount on DIN rail (TS 35 x 7.5 or TS 35 x 15)
- Maintain minimum 10 mm spacing between modules for heat dissipation
- Use shielded cables for analog signal wiring
- Connect cable shield to ground at one end only (controller side)
- Connect to X20 system base module
Usage Precautions:
- Never apply voltage exceeding 30 V DC to any input terminal
- For 4-20 mA inputs, ensure loop power is provided externally
- Verify input range setting matches connected transmitter output
- Do not leave current input terminals open-circuited when loop is energized