Detailed content
- Channel Count: 2 analog outputs
- Output Type: 4–20 mA (configurable to 0–20 mA)
- Resolution: 12-bit (4096 steps)
- Output Accuracy: ±0.1% of full scale
- Load Impedance: Up to 600 Ω (at 24 V DC supply)
- Isolation: 500 V DC between channels and backplane
- Power Supply: 5 V DC from backplane bus
- Current Consumption: 380 mA from 5 V bus
- Operating Temperature: 0°C to +60°C
- Storage Temperature: -40°C to +85°C
- Humidity: 5% to 95% RH (non-condensing)
- Dimensions (HxWxD): 98 x 23 x 120 mm
- Weight: 0.12 kg
- Standards: IEC 61131-2, CE, UL, CSA, ATEX (Zone 2)
Functional Features:
- Diagnostics: Per-channel wire break detection, short-circuit detection, overrange/underrange indication
- Configuration: Set via Unity Pro software or front-panel DIP switches
- Update Rate: 2 ms per channel (simultaneous update)
- Hot Swap: Module can be replaced without CPU stop (with Quantum backplane)
Structure:
- 2 × 3-wire terminal blocks (for 4–20 mA output)
- 1 × 40-pin backplane connector
- LED status indicators per channel (green = OK, red = fault)
Applicable Industries:
- Process control (flow, pressure, temperature transmitters)
- Building automation (damper actuators, valve control)
- Power generation (turbine governor control)
- Oil & gas (remote I/O applications)
Installation Requirements:
- Insert into Quantum backplane rack (no screw mounting required)
- Connect shield wire to chassis ground at one end only
- Configure output range in software before commissioning
Usage Notes:
- Do not exceed 600 Ω total loop resistance
- Use shielded twisted-pair cable for noise-sensitive environments
- Calibrate zero and span at installation for best accuracy