Digital guide

You are here:

AEG MM-PM10-300

Product Name: AEG MM-PM10-300 Motor Protection Relay (Motor Management Relay)
Product Category: Motor Protection / Monitoring Device
Model Series: AEG MM-PM10 Series
Current Range: 0.1 – 300A (via external CT)
Protection FunctionsOverload, Short-Circuit, Phase Loss, Phase Reversal, Ground Fault

Detailed content

Product Description:
The AEG MM-PM10-300 is a microprocessor-based motor protection relay from the AEG MM series, designed for comprehensive protection and monitoring of three-phase AC induction motors. It continuously monitors motor current and provides multiple protection functions with adjustable trip settings. The “300” designation indicates a maximum current measurement range of 300A (via external current transformers).

Technical Specifications:

  • Current Measurement Range: 0.1A – 300A (via external CT, ratio selectable: 50/5A to 600/5A)
  • Voltage Input: 100V – 690V AC (3-phase, direct connection or via PT)
  • Auxiliary Power Supply24V – 240V AC/DC (universal)
  • Overload Protection (Class 10 / Class 20 / Class 30): Adjustable trip current: 0.4 – 1.0 × In; Trip time: 2 – 30 seconds (inverse time)
  • Short-Circuit Protection (Instantaneous): Adjustable: 2 – 15 × In; Trip time: ≤ 20ms
  • Phase Loss Protection: Detects loss of any one phase; Trip delay: 0.5 – 30s (adjustable)
  • Phase Reversal Protection: Detects incorrect phase sequence; Trip: instantaneous
  • Ground Fault Protection (Sensitive): Adjustable: 0.1 – 1.0 × In; Trip time: ≤ 100ms
  • Thermal Model: I²t thermal motor model with thermal memory (RTD/PTC input optional)
  • Digital Inputs: 3× DI (motor start/stop, reset, external fault)
  • Digital Outputs: 2× DO (trip relay + alarm relay), Rating: 5A / 250V AC (resistive)
  • CommunicationRS-485 (Modbus RTU), baud rate: 9600 – 115200 bps
  • Accuracy: ±1% (current), ±0.5% (voltage)
  • Standards Compliance: IEC 60947-6-2, IEC 60255, EN 60947-6-2, UL 508
  • Protection RatingIP20 (front panel), IP40 (with cover)
  • Installation: DIN 35mm rail (EN 60715 TH35)
  • Dimensions (W×H×D)72mm × 105mm × 110mm
  • Weight: ~400g

Protection Functions Detail:

Function Setting Range Trip Time
Overload (L) 0.4–1.0 × In Inverse time (2–30s)
Short Circuit (I) 2–15 × In ≤ 20ms (instantaneous)
Phase Loss (Δ) 0.5–30s delay Adjustable
Phase Reversal (↔) Instantaneous ≤ 50ms
Ground Fault (G) 0.1–1.0 × In ≤ 100ms
Unbalance (U) 5–30% current unbalance 2–30s
Lock Rotor (LR) 4–8 × In 0.5–5s
Start Time Monitor 0.5–60s Adjustable

Material Composition:

  • Housing: Polycarbonate (PC) + ABS blend — UL94 V-0, halogen-free
  • Terminals: Tin-plated copper alloy, screw terminal (1.5–4mm²)
  • Display: Front-panel LED indicators (Power, Run, Trip, Alarm) + optional LCD display variant

Structural Features:

  • DIN rail mounting with snap-lock mechanism
  • Front-accessible terminal connection (no rear wiring required)
  • Rotary dial + push-button for parameter setting (no PC software required for basic configuration)
  • Optional LCD display module for real-time current/voltage readout

Advantages:

  • 7 independent protection functions in a single device
  • Adjustable trip settings without external software (rotary dial + buttons)
  • 0.1–300A wide current range — covers motors from 0.18kW to 250kW+
  • RS-485 Modbus RTU for SCADA/DCS integration
  • Universal 24–240V AC/DC power supply
  • Thermal memory function — prevents nuisance tripping after motor cooldown

Applicable Industry:

  • Pump station motor protection
  • Compressor motor protection
  • Conveyor belt drive systems
  • HVAC chiller and fan motor protection
  • Mining and heavy industry motor control
  • Water/wastewater treatment motor protection