Product Overview:
The AEG C916-100 is a motor protection circuit breaker (MPCB) designed to protect three-phase AC motors from overload, short-circuit, and phase-failure conditions. It combines the functions of a circuit breaker, overload relay, and phase-failure monitor in a single device, eliminating the need for separate components.
Technical Specifications:
- Rated Current (Ir): 100 A
- Poles: 3P (Three Pole)
- Rated Voltage (Ue): 690V AC (50/60 Hz)
- Rated Short-Circuit Breaking Capacity (Icu): 50 kA at 690V
- Rated Ultimate Breaking Capacity (Icu): 50 kA
- Rated Operational Breaking Capacity (Ics): 100% of Icu (50 kA)
- Trip Current Range (Ir): 80 A – 100 A (adjustable via dial)
- Trip Class: 10 (trips within 10 seconds at 7.2× Ir)
- Phase-Failure Protection: Built-in, adjustable 20%–40% voltage unbalance
- Mechanical Life: 10,000 operations
- Electrical Life: 5,000 operations at rated current
- Dimensions (W×H×D): 106 mm × 138 mm × 110 mm
- Mounting: DIN rail (35 mm) or screw mounting
- Weight: Approximately 1.8 kg
Material Composition:
- Housing: Glass-fiber reinforced polyamide (PA66-GF30), flame-retardant UL94 V-0
- Contacts: Silver-tungsten alloy (AgW10) for high breaking capacity
- Arc Chute: 12 stainless steel de-ion plates per pole
- Trip Unit: Electronic-thermal hybrid with microprocessor
- Terminals: Copper alloy, screw terminal, max 70 mm² conductor
Structural Features:
- Front-mounted rotary dial for current setting (80–100 A)
- LED indicator: green = powered, yellow = pre-alarm, red = tripped
- Test button for functional verification of trip mechanism
- Screw-clamp terminals for ring or fork connectors
- IP20 front panel protection (must be installed in enclosure for IP rating)
Working Principle:
- Overload Protection: Thermal-magnetic trip unit monitors current continuously. When current exceeds set Ir for duration defined by trip class 10 curve, the bimetallic element triggers release.
- Short-Circuit Protection: Electromagnetic instantaneous trip activates at 10× Ir or above, opening all three poles within 10 ms.
- Phase-Failure Protection: Built-in voltage monitor detects loss of any phase or voltage drop below 60% of nominal. Trips within 0.5 seconds to prevent single-phasing motor damage.
- Arc Extinction: 12 de-ion plates per pole split and cool the arc, enabling 50 kA safe interruption.
Key Advantages:
- All-in-one solution — replaces MCB + overload relay + phase-failure relay (saves panel space and wiring cost)
- 50 kA breaking capacity suitable for industrial distribution boards close to transformer
- Adjustable trip range (80–100 A) covers multiple motor sizes with one device
- Trip class 10 perfectly matched to motor thermal withstand curves (IEC 60947-4-1)
Applicable Industries:
- Industrial motor control centers (MCC)
- Pump station motor protection
- Compressor motor protection
- Conveyor drive protection
- HVAC chiller motor protection
Installation Requirements:
- Mount on 35 mm DIN rail or panel-mount with 4×M6 screws
- Connect L1/L2/L3 motor lines to load terminals (bottom)
- Connect supply to line terminals (top)
- Torque terminals to 6 Nm for 70 mm² conductors
- Coordinate with upstream 125 A or 160 A MCCB for selective discrimination
Usage Precautions:
- Set trip dial to exact motor FLA (Full Load Amperage) — do not oversize
- Test trip function monthly using test button
- After any short-circuit trip, replace the unit — internal arc damage is not visible
- Ensure enclosure provides at least IP54 protection if installed in wet environment