Detailed content
Output Signal: 4-20 mA (isolated, two-wire)
Supply Voltage: 24 V DC (±10%)
Isolation Voltage: 1500 V DC (input to output to power)
Accuracy: ±0.1% of span (at 25°C)
Temperature Drift: ±0.015% of span / °C
Response Time: ≤ 10 ms (0 to 90% step change)
Load Capacity: Maximum 600 Ω at 24 V DC supply
Protection Class: IP20 (DIN rail mount enclosure)
Operating Temperature: -20°C to +60°C
Storage Temperature: -40°C to +85°C
Mounting: 35 mm DIN rail (EN 60715)
Dimensions (W × H × D): 22.5 mm × 90 mm × 112 mm
Housing Material: Polycarbonate (UL94 V-0 flame rating)
Key Features:
- Galvanic isolation prevents ground loop interference
- Loop-powered — no separate power supply required for field devices
- Conformal coated PCB for humidity and dust resistance
- DIP switch selectable: input/output range scaling (0-10 mA, 4-20 mA, 0-20 mA)
Applicable Industries: Process control, water/wastewater treatment, oil & gas, power generation, building automation
Installation Requirements:
- Mount on DIN rail 35 mm, TS 35/7.5 or TS 35/15
- Maintain minimum 10 mm clearance above and below module for ventilation
- Use shielded twisted-pair cable for signal lines (max 500 m run)
- Ground shield at one end only (drive end)
Usage Notes:
- Do not exceed 600 Ω total loop resistance (including wire resistance)
- Verify polarity before energizing — reverse polarity causes no output
- Calibrate zero and span using front-panel potentiometers annually