Detailed content
Model Difference
8406-120: 150 to 300 Vac PT input
8406-121: 50 to 150 Vac PT input
Both: 9 to 32 Vdc control power
Engine Control
Start/stop
Crank control
Fuel solenoid control
Pre-glow control
Speed monitoring
Overspeed protection
Oil pressure monitoring
Coolant temperature monitoring
Battery voltage monitoring
Synchronizing
Phase angle matching
Voltage matching
Frequency matching
Safe dead-bus closing
Auto-resynchronizing
Sync-check protection
Real Power Control
True RMS kW calculation
Isochronous load sharing up to 8 units
Base load control
Droop control
Import/export control with external watt transducer
Process control using 4 to 20 mA feedback
Reactive Power Control
kVAR control
Power factor control
VAR sharing on isolated buses
Protection Functions
Over/under voltage
Over/under frequency
Reverse power
Reverse VARs
Overcurrent
Loss of mains
Overload
Speed/frequency mismatch
Operator Interface
LCD display
Keypad
Status LEDs
Alarm history
Event log
Capacity
Generator sets from 400 to 3600 rpm
Up to 30,000 kW generator sets
Up to 8 EGCP-2 units in a network
Application Scenarios
Diesel generator sets
Gas generator sets
Standby power systems
Prime power plants
Parallel generator boards
Cogeneration plants
Peak shaving systems
Microgrid controllers
Working Principle
The EGCP-2 measures generator voltage, current, frequency, and engine speed. It calculates active and reactive power, compares actual values with setpoints, and adjusts governor and excitation control to maintain frequency, voltage, kW, kVAR, or power factor.
Installation Requirements
Suitable for non-hazardous locations.
Field wiring must meet applicable electrical codes.
Use conductors rated for at least 90 °C.
Verify PT ratio and CT ratio before commissioning.
Provide 9 to 32 Vdc control power.
Use single-point grounding and surge suppression in noisy sites.
Usage Notes
Never close the generator breaker without sync check.
Verify reverse power and loss-of-mains settings.
Test alarm, trip, and unload functions before live operation.
Back up configuration before changing protection setpoints.
Only qualified personnel may adjust control and protection parameters.