Woodward 9908-217
Product Name: LQ25 Liquid Fuel Metering Valve (Enhanced Configuration)
Product Overview: 9908-217 is an LQ25-series liquid fuel metering valve with refined metering characteristics. It adopts a rotary-plate metering structure integrating a Limited-Angle Torque (LAT) motor, frameless resolver feedback, and optional PIV / SOV interfaces.
Detailed content
Key Technical Specifications:
-
Metering Accuracy: ±5% of nominal flow or ±0.5% of maximum rated flow (larger value applies)
-
Full-Stroke Swivel Time: <100 ms
-
Shutoff Swivel Time: <50 ms
-
Shutoff Response (close): <100 ms
-
Maximum Fuel Inlet Pressure: 1,200 psig (8,274 kPa)
-
Nominal Metering ΔP: 50 psid (345 kPa)
-
Minimum Metered Flow: 80 lb/h (36 kg/h)
-
Turndown Ratio: >100:1
-
Fuel Filtration: ≤20 µm
-
Water Content: ≤0.1% by volume
-
Drive Voltage: 18–32 VDC
-
Command / Feedback: 4–20 mA
-
Ingress Protection: IP66
-
Operating Temperature: –28 °C to +85 °C
-
Storage Temperature: –40 °C to +103 °C
-
Fuel Connection: SAE J1926/1 threaded
Materials & Structure: The valve body and wetted components use corrosion-resistant materials or anti-corrosion treatment; seals are FKM fluoro-carbon rubber suitable for a wide range of liquid fuels. The overall structure is a rotary-plate metering design integrating a Limited-Angle Torque motor, frameless resolver feedback, and optional PIV/SOV mounting interfaces.
Working Principle: The drive unit receives a 4–20 mA position command and, through closed-loop control, drives the limited-angle torque motor to rotate the rotary plate, changing the metering port area. The patented single-stage droop-compensated differential pressure regulator holds the metering-port ΔP at approx. 345 kPa (50 psid), so that output flow is governed solely by port area, achieving precise metering.
Installation Requirements: Must be used with a positive-displacement fuel pump—not compatible with other pump types. Fix the valve to a rigid foundation via standard mounting holes; orient for ease of maintenance. Electrical connection is made through a single terminal block; use shielded cable between driver and valve body. Wear hearing protection on-site.
Usage Precautions: Fuel must be filtered to ≤20 µm with water content ≤0.1% by volume. Regularly check electrical-connection tightness and cable-shield integrity. Avoid long-term operation outside the specified temperature envelope. Before maintenance, cut fuel supply and confirm the system is depressurized.