Digital guide

You are here:

Woodward 9907-687

  • Product Name (reference):​ MSLC Master Synchronizer and Load Control
  • Product Introduction:​ A microprocessor-based overall plant load control designed for use with Woodward DSLC controls on each generator, providing utility synchronizing, paralleling, loading/unloading of a three-phase generating system.

Detailed content

  • Technical Specifications (reference MSLC platform):
    • Power Supply: 120/240 VAC (model-dependent)
    • Operating Temperature: –40 to +70°C
    • Storage Temperature: –55 to +105°C
    • Humidity: 95% RH at 38°C
    • CT Input: 0–5 A, max 7 A; burden <0.1 VA per phase
    • EMS: ANSI/IEEE C37.90.2; ANSI C37.90.1-1989
    • Certifications: UL and cUL listed
  • Functional Features:
    • Phase matching or slip-frequency synchronizing with voltage matching
    • Automatic system loading/unloading for bumpless load transfer
    • Import/Export level control
    • Process control for cogeneration, pressure, or other processes
    • Proportional loading of associated DSLC controls in isochronous load sharing
    • Adjustable power factor control
    • Multi-function adjustable high/low limit alarms and load switches with relay driver outputs
    • Digital communications network (LonWorks) to DSLC-equipped generators
    • Full setup, metering, and diagnostics via handheld programmer
  • Working Principle:​ Uses digital signal processing to derive true RMS voltages and relative phase angles of utility and local bus waveforms. Generates raise/lower signals to DSLC speed controls and voltage regulators for automatic synchronization and load sharing.
  • Application Scenarios:​ Three-phase generating plants with multiple DSLC-controlled generators paralleling to utility; cogeneration facilities; import/export power management.
  • Installation Requirements:​ Install per Woodward MSLC manual 02022; proper grounding and shielded wiring for PT/CT inputs; LonWorks network cabling to individual DSLC units.
  • Usage Notes:​ Verify the specific voltage configuration (120 V vs 240 V, Wye vs Delta) before installation; do not remove PCB from cabinet except when necessary, and follow ESD precautions; confirm 9907-687’s exact configuration with Woodward documentation.