Detailed content
-
Technical Specifications (reference 505/505E):
-
Power: 18–32 Vdc, 90–150 Vdc, 88–132 Vac, or 180–264 Vac (47–63 Hz)
-
Operating Temperature: –40 to 70°C
-
Humidity: 5–95% RH non-condensing
-
Vibration: 2 g; Shock: 15 g, 11 ms
-
Communication: 2 × Modbus (RS-232/422/485, ASCII/RTU)
-
Speed Sensing: 2 MPU or proximity probes, 0.5–15 kHz
-
PIDs: Speed/Load (dual dynamics), Auxiliary, Cascade
-
Protection: Integral overspeed logic, 10 first-out shutdown inputs, failsafe shutdown
-
-
Functional Features: Three PIDs (Speed, Auxiliary, Cascade); critical speed avoidance; speed control; cascade control; overspeed test; valve limiting; frequency control; Modbus communications; accepts 4–20 mA speed command from DCS.
-
Application Scenarios: Steam turbine control for power generation and mechanical drive; ship propulsion; offshore platform backup power.
-
Installation & Usage Notes: Mount in panel; use pluggable terminal blocks for easy wiring; independent overspeed trip mandatory; read full manual before installation or service.