Digital guide

You are here:

Woodward 9907-535

Product Name:​ Woodward 2301A-LS Low-Voltage Load Sharing Controller
Product Introduction:​ A derivative model of the 2301A series, focusing on multi-unit load sharing. It simplifies some synchronization functions and specializes in prime mover speed closed-loop and parallel load sharing, suitable for scenarios requiring multi-unit island parallel operation without complex grid-tie logic.

Detailed content

Technical Specifications:
  • Power Supply: 18–40 VDC
  • Speed Sensing: Magnetic pickup input
  • Drive Output: Proportional actuator drive output
  • Operating Temperature: -40°C to +85°C
  • Enclosure Rating: IP20
Functional Features:
  • High-precision speed closed-loop control with isochronous/droop mode switching
  • Multi-unit island parallel load sharing
  • Hardware self-test alarm output
  • External potentiometer for parameter setting
  • No complex synchronization logic, simple and reliable hardware structure
Application Scenarios:​ Offshore platform island power generation, mining mobile power stations, multi-unit island backup power supplies.
Material Composition:​ Sheet metal enclosure, single industrial PCB, flame-retardant terminals.
Structural Features:​ Cabinet-embedded single-board installation; no local display panel.
Working Principle:​ Acquires speed signals for closed-loop actuator output adjustment; exchanges load signals from each unit via the load sharing bus and dynamically corrects output to achieve load sharing in island mode.
Installation Requirements:
  • Install inside a sealed control cabinet; direct installation on the engine body is prohibited
  • Speed signal lines and load bus must use shielded twisted-pair cable with single-point grounding
  • Keep away from high-voltage interference sources; reserve heat dissipation space
Usage Precautions:
  • No synchronization closing logic; this model is not applicable to grid-tie scenarios
  • The system must be equipped with an independent hardware overspeed protection device
  • Anti-static protection during assembly/disassembly; power polarity must not be reversed