Technical SpecificationsWoodward:
  • Supply Voltage: 18–32 VDC
  • Input Signal: 4–20 mA (isolated)
  • Output Pressure Range: 0–10 bar (0–145 psi)
  • Supply Pressure: 11–13 bar (160–189 psi)
  • Accuracy: ±0.15% of full span
  • Operating Temperature: -40°C to +85°C
  • Housing: Rugged, explosion-proof aluminum
  • Weight: 2.3 kg
  • Certifications: ATEX, IECEx (Zone 1), CE

    Functional FeaturesWoodward:

  • Enhanced dynamics (ED) for fast and stable control
  • Patented self-cleaning spool valve (resistant to 40 µm particles)
  • Zone 1 certified for explosive gas atmospheres
  • Linear output characteristic across full pressure range
  • Built-in diagnostics and health monitoring
  • Supports simplex (single) configurations
  • Compatible with mineral and synthetic hydraulic oils

    Applications:

  • Steam turbine speed/load control in hazardous areas
  • Oil and gas production facilities
  • Petrochemical and chemical processing plants
  • Industrial power generation
  • Critical turbine control systems