Honeywell XFR824A
Product Introduction
The XFR824A belongs to the Honeywell Excel 800 controller platform as the Panel Bus relay output module providing six relay outputs with manual overrides. The Excel 800 system offers freely programmable, high-performance and cost-effective control for HVAC systems and energy management applications. The module is pluggable onto a terminal socket so that field wiring can be completed before the module is inserted, and it can be maintained or replaced without interrupting power or network.
Detailed content
Technical Specifications
Order number: XFR824A. Description: Panel Bus relay output module with 6 relay outputs with manual overrides. Number of relay outputs: 6. Manual override: one switch per output with auto feedback signal carrying mode and value. Status indication: two LEDs per output, green for relay 1 closed and red for relay 2 closed, blinking in the manual override position. Mounting: plug-in module on the corresponding Panel Bus terminal socket. Configuration: via the Excel 800 controller, with CARE software for LonWorks modules.
Functional Features
Pluggable relay output module with per-output manual override switches supporting direct local operation as per EN ISO 16484-2:2004, section 5.4.3. Dual-LED indication per output showing relay state. Automatic feedback of manual override mode and position to the controller for storage in the alarm memory. Panel Bus plug-and-play with manual address setting through a HEX switch, or automatic configuration by the controller for Panel Bus modules.
Performance Parameters
Six relay output channels. Manual override switch behavior specified with OFF greater than 90 kΩ to ground or greater than 4 V to ground for the switch position. Relay contacts rated for switching the connected field loads within the Excel 800 module specification.
Material Composition
Pluggable electronic module with front-panel override switches and LEDs, mounted on a terminal socket that carries the field wiring terminals, bridge connector and swivel label. Relay contacts and electronic drive circuitry integrated within the module.
Structural Characteristics
Two-piece pluggable construction with terminal socket plus removable module, front-accessible manual override switches, and dual LED indicators per output for relay state and override status.
Working Principle
The XFR824A receives relay output commands over the Panel Bus from the Excel 800 controller and energizes or de-energizes the six relay contacts to switch field loads such as fans, pumps and other on/off equipment. When an override switch is moved from the automatic position, the module directly controls the corresponding relay independently of the controller, blinks the associated LED, and reports the override mode and position back to the controller.
Installation Requirements
Install on the appropriate Panel Bus terminal socket with wiring completed before module insertion. Indoor control cabinet installation. Set the HEX switch address for Panel Bus modules. Ambient operating temperature within the module specification.
Application Scenarios
HVAC equipment on/off control, pump and fan staging, energy management sequences, and building automation applications requiring local manual override of relay outputs during commissioning, maintenance or controller failure.