Digital guide

You are here:

Woodward 8915-919

Product Introduction
The Woodward 8915-919 is a fully electric fuel metering valve assembly of the 3103 valve family, driven by an EM35MR all-electric actuator. Configured for explosion-proof area applications, it is designed to pair with the Woodward NetCon system, serving fuel metering and control in gas turbines across power generation, chemical processing, and oil & gas transmission fields.

Detailed content

Technical Specifications
  • Pressure Rating: CE limited to 4964 kPa (720 psia); Enhanced up to 6205 kPa gauge (900 psig)
  • Differential Pressure Range: 172 to 6205 kPa (25 to 900 psi)
  • Fuel Temperature: –40 to +149 °C
  • Ambient Temperature: –40 to +93 °C
  • Metered Fuel Types: Natural gas, propane, methane
  • Fuel Specific Gravity: 0.5 to 1.05
  • Fuel Filtration: 25 µm absolute (β = 75)
  • Flow Accuracy: ±5% of point or ±0.25% of maximum flow; ±2% of point for DLE applications
  • Minimum Differential Pressure: 172 kPa (non-DLE), 345 kPa (DLE)
  • Output Shaft Rotation: 60°
  • Continuous Output Torque: ±24.9 N·m (±220 lb-in)
  • Peak Output Torque: ±62.4 N·m (±552 lb-in)
  • Clutch Disengagement Torque: ±68 N·m (±600 lb-in)
  • Torque Constant: 1.8 N·m/A
  • Motor Type: Brushless DC motor, samarium-cobalt permanent magnet
  • Power Input: 28 Vdc nominal, 18 to 32 Vdc operating range
  • Current: Max 37 A (50 ms), max continuous 15 A
  • Slew Rate: 50° stroke — 150 ms opening, 80 ms closing
  • Bandwidth: > 5 Hz
  • Position Accuracy: ±0.50° analog, ±0.10° digital
  • Resolver Accuracy: ±0.05°
  • Assembly Weight: Approx. 44 kg (96 lb)
  • Fuel Connection: 2-inch 600# ANSI B16.5 flange
Material Composition
  • Valve Body: Stainless steel
  • Internal Components: Fully hardened stainless steel throughout
  • Actuator Housing: Cast aluminum flameproof enclosure
  • Motor: Samarium-cobalt permanent magnet brushless DC motor
  • Resolver: Non-contact electromagnetic induction structure
Structural Features
  • Planetary gear reduction actuator directly coupled to valve body
  • Resolver detects metering sleeve position
  • Inlet flow guide tube with redundant sealing design
Working Principle
The controller signal drives the motor to change the valve sleeve opening. The resolver provides feedback for closed-loop control. On fault, a spring closes the valve to the minimum fuel position.
Functional Features
  • Fully electric drive, no hydraulic oil source
  • Brushless DC motor with samarium-cobalt magnets, stator windings fully encapsulated
  • High-precision brushless resolver, non-contact position feedback
  • Built-in slip clutch protects transmission
  • Fault detection and automatic protection
  • Spring return to minimum fuel on power loss
  • Analog 4–20 mA or digital control mode
  • Flameproof design with CSA and ATEX certification
  • Self-cleaning metering structure for sour gas service
Application Scenarios
  • Explosion-proof area applications
  • Paired with Woodward NetCon system
  • Power generation, chemical processing, oil & gas transmission
Installation Requirements
  • Flameproof cover plate bolts tightened to specified torque
  • Explosion-proof cable glands and conduit sealing
  • Use auxiliary equipment for lifting during handling
  • Proper grounding system connection
  • 25 µm absolute filtration at fuel inlet
Usage Notes
  • Motor cables must not be coiled
  • Maintenance in explosion-proof areas requires power disconnect
  • Regularly inspect cable connections
  • Surface temperature protection
  • Mechanical stops must not be adjusted
  • Inspect flexibility after prolonged shutdown