Woodward 8915-914
Product Name: Woodward 8915-914 — 1907 Large Liquid Valve & Actuator Assembly
Product Description: The 8915-914 is a 1907 Large Liquid Valve & Actuator assembly for gas turbine liquid fuel metering applications. It provides the same core functionality and technical performance as other 1907 Large Liquid Valve & Actuator units in this series.
Detailed content
Technical Specifications:
-
Metered Fuel Flow: 30:1 turndown, maximum 11,340 kg/h (25,000 lb/h)
-
Minimum Fuel Flow: 68 kg/h (150 lb/h)
-
Fuel Inlet Pressure (Maximum): 9,377 kPa (aluminum body) / 17,238 kPa (stainless steel body)
-
Differential Pressure: 345 to 827 kPa
-
Fuel Viscosity: 0.5 to 12.0 centistokes
-
Fuel Specific Gravity: 0.77 to 0.91
-
Cleanliness: 20 μm filtration, water ≤0.1%, particulates ≤1.0 mg/L
Fuel Compatibility: Diesel, kerosene, gasoline, light/heavy distillates, naphtha, gas turbine fuels, fuel oils, biodiesel compatible with FKM elastomers.
Functional Features:
-
Differential pressure regulated constant flow metering
-
Precision valve positioning via integrated actuator
-
Stable fuel delivery independent of system pressure variations
Application Scenarios: Gas turbine liquid fuel control across power generation, oil & gas, marine, and industrial turbine applications.
Material Composition: Aluminum or stainless steel valve body; through-hardened stainless steel internals; FKM seals.
Working Principle: The integrated actuator positions the 1907 valve plunger. The differential pressure regulator maintains constant pressure drop across the metering port, delivering consistent fuel flow proportional to valve position.
Installation Requirements:
-
Install valve square with governor/actuator linkage to prevent binding
-
Allocate actuator travel: two-thirds between minimum and maximum; remaining third split at endpoints
-
Use shielded electrical wiring
-
Follow Woodward outline drawings and control wiring diagrams
Usage Precautions:
-
Maintain fuel filtration at 20 μm or finer
-
Limit water content to 0.1% by volume; particulates to 1.0 mg per liter
-
Read entire manual and all related publications before installing, operating, or servicing
-
Practice all plant and safety instructions and precautions
-
Failure to follow instructions can cause personal injury and/or property damage